B Parameter Table

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

199

Pa

ra

me

te

r T

abl

e

B

o3: Copy Function

o4: Maintenance Monitor Settings

No.

(Addr.)

Name

Description

Setting

o3-01

(515H)

Copy Function Selection

0: Copy select
1: INV

→ OP READ (Read parameters from the drive, saving them onto the

digital operator.)
2: OP

→ INV WRITE (Copy parameters from the digital operator, writing them

to the drive.)
3: OP

↔ INV VERIFY (Verify parameter settings on the drive to check if they

match the data saved on the operator.)
To read the drive’s parameter settings into the digital operator, set o3-02 to 1 (to
allow reading).

Default: 0
Min: 0
Max: 3

o3-02

(516H)

Copy Allowed Selection

Selects whether the read operation (o3-01 = 1) is enabled or disabled.
0: Read operation prohibited
1: Read operation allowed

Default: 0
Min: 0
Max: 1

No.

(Addr.)

Name

Description

Setting

o4-01

(50BH)

Cumulative Operation Time
Setting

Sets the value for the cumulative operation time of the drive in units of 10 h.

Default: 0
Min: 0
Max: 9999

o4-02

(50CH)

Cumulative Operation Time
Selection

0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).

Default: 0
Min: 0
Max: 1

o4-03

(50EH)

Cooling Fan Operation Time
Setting

Sets the value of the fan operation time monitor U4-03 in units of 10 h.

Default: 0 h
Min: 0 h
Max: 9999 h

o4-05

(51DH)

Capacitor Maintenance
Setting

Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to
check when the capacitors may need to be replaced.

Default: 0%
Min: 0%
Max: 150%

o4-07

(523H)

DC bus Pre-charge Relay
Maintenance Setting

Sets the value of the Maintenance Monitor for the soft charge bypass relay. See
U4-06 to check when the bypass relay may need to be replaced.

Default: 0%
Min: 0%
Max: 150%

o4-09

(525H)

IGBT Maintenance Setting

Sets the value of the Maintenance Monitor for the IGBTs. See U4-07 to check
when the IGBTs may need to be replaced.

Default: 0%
Min: 0%
Max: 150%

o4-11

(510H)

U2, U3 Initialization

0: U2-

and U3-

monitor data is not reset when the drive is initialized

(A1-03).
1: Resets the data for the U2-

and U3-

monitors. Once o4-11 is set to 1

and the ENTER key is pressed, fault data is erased and the display returns to 0.

Default: 0
Min: 0
Max: 1

o4-12

(512H)

kWh Monitor Initialization

0: U4-10 and U4-11 monitor data is not reset when the drive is initialized (A1-
03).
1: Resets the kWh counter. The monitors U4-10 and U4-11 will display "0" after
they are initialized. Once o4-12 is set to 1 and the ENTER key is pressed, kWh
data is erased and the display returns to 0.

Default: 0
Min: 0
Max: 1