B parameter table – Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 199
B Parameter Table
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
199
Pa
ra
me
te
r T
abl
e
B
o3: Copy Function
o4: Maintenance Monitor Settings
No.
(Addr.)
Name
Description
Setting
o3-01
(515H)
Copy Function Selection
0: Copy select
1: INV
→ OP READ (Read parameters from the drive, saving them onto the
digital operator.)
2: OP
→ INV WRITE (Copy parameters from the digital operator, writing them
to the drive.)
3: OP
↔ INV VERIFY (Verify parameter settings on the drive to check if they
match the data saved on the operator.)
To read the drive’s parameter settings into the digital operator, set o3-02 to 1 (to
allow reading).
Default: 0
Min: 0
Max: 3
o3-02
(516H)
Copy Allowed Selection
Selects whether the read operation (o3-01 = 1) is enabled or disabled.
0: Read operation prohibited
1: Read operation allowed
Default: 0
Min: 0
Max: 1
No.
(Addr.)
Name
Description
Setting
o4-01
(50BH)
Cumulative Operation Time
Setting
Sets the value for the cumulative operation time of the drive in units of 10 h.
Default: 0
Min: 0
Max: 9999
o4-02
(50CH)
Cumulative Operation Time
Selection
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).
Default: 0
Min: 0
Max: 1
o4-03
(50EH)
Cooling Fan Operation Time
Setting
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
Default: 0 h
Min: 0 h
Max: 9999 h
o4-05
(51DH)
Capacitor Maintenance
Setting
Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to
check when the capacitors may need to be replaced.
Default: 0%
Min: 0%
Max: 150%
o4-07
(523H)
DC bus Pre-charge Relay
Maintenance Setting
Sets the value of the Maintenance Monitor for the soft charge bypass relay. See
U4-06 to check when the bypass relay may need to be replaced.
Default: 0%
Min: 0%
Max: 150%
o4-09
(525H)
IGBT Maintenance Setting
Sets the value of the Maintenance Monitor for the IGBTs. See U4-07 to check
when the IGBTs may need to be replaced.
Default: 0%
Min: 0%
Max: 150%
o4-11
(510H)
U2, U3 Initialization
0: U2-
and U3-
monitor data is not reset when the drive is initialized
(A1-03).
1: Resets the data for the U2-
and U3-
monitors. Once o4-11 is set to 1
and the ENTER key is pressed, fault data is erased and the display returns to 0.
Default: 0
Min: 0
Max: 1
o4-12
(512H)
kWh Monitor Initialization
0: U4-10 and U4-11 monitor data is not reset when the drive is initialized (A1-
03).
1: Resets the kWh counter. The monitors U4-10 and U4-11 will display "0" after
they are initialized. Once o4-12 is set to 1 and the ENTER key is pressed, kWh
data is erased and the display returns to 0.
Default: 0
Min: 0
Max: 1