A Specifications

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

161

S

p

ec

ifi

c

at

ions

A

Drive Specifications

Note: 1. Perform rotational Auto-Tuning to obtain the performance specifications given below.

2. For optimum performance life of the drive, install the drive in an environment that meets the required specifications.

Item

Specification

Control
Characteristics

Control Method

The following control methods can be set using drive parameters:

• V/f Control (V/f)
• Open Loop Vector Control (OLV)
• Closed Loop Vector Control (CLV)
• Closed Loop Vector Control for PM (CLV/PM)

Frequency Control Range

0.01 to 120 Hz

Frequency Accuracy
(Temperature Fluctuation)

Digital input: within ±0.01% of the max output speed (-10 to +40 °C)
Analog input: within ±0.1% of the max output speed (25 °C ±10 °C)

Frequency Setting
Resolution

Digital inputs: 0.01 Hz
Analog inputs: 1/2048 of the maximum output speed setting (11 bit plus sign)

Output Speed Resolution

0.001 Hz

Frequency Setting Signal

Main speed frequency reference: DC -10 to +10 V (20 k

Ω), DC 0 to +10 V (20 kΩ), 4 to 20

mA (250

Ω), 0 to 20 mA (250 Ω)

Starting Torque

<1>

V/f: 150% at 3 Hz
OLV: 200% at 0.3 Hz
CLV, CLV/PM: 200% at 0 r/min

Speed Control Range

<1>

V/f: 1:40
OLV: 1:200
CLV, CLV/PM: 1:1500

Speed Control Accuracy

<1>

OLV:

±0.2% (25°C ±10°C)

CLV:

±0.02% (25°C ±10°C)

Speed Response

<1>

OLV: 10 Hz (25°C ±10°C)
CLV: 50 Hz (25°C ±10°C)

Torque Limit

Parameters setting allow separate limits in four quadrants (available in OLV, CLV, CLV/PM)

Control
Characteristics

Accel/Decel Ramp

0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration
settings, unit changeable to m/s

2

or ft/s

2

)

Braking Transistor

Models CIMR-LE2A0018 to 2A0144, 4A0009 to 4A0075 have a built-in braking transistor.

V/f Characteristics

Freely programmable

Main Control Functions

Inertia Compensation, Position Lock at Start and Stop/Anti-Rollback Function, Overtorque/
Undertorque Detection, Torque Limit, Speed Reference, Accel/decel Switch, 5 Zone Jerk
Settings, Auto-Tuning (Stationary and Rotational Motor/Encoder Offset Tuning), Dwell,
Cooling Fan on/off Switch, Slip Compensation, Torque Compensation, DC Injection Braking
at Start and Stop, MEMOBUS/Modbus Comm. (RS-422/485 max, 115.2 kbps), Fault Reset,
Removable Terminal Block with Parameter Backup Function, Online Tuning, High
Frequency Injection, Short Floor, Rescue Operation (Light Load Direction Search Function),
Inspection Run, Brake Sequence, Speed related parameters with elevator units display, etc.

Protection
Functions

Motor Protection

Electronic thermal overload relay

Momentary Overcurrent
Protection

Drive stops when output current exceeds 200% of rated output current

Overload Protection

Drive stops after 30 s at 133% of rated output current

<2>

Overvoltage Protection

200 V class: Stops when DC bus voltage exceeds approx. 410 V
400 V class: Stops when DC bus voltage exceeds approx. 820 V

Undervoltage Protection

200 V class: Stops when DC bus voltage falls below approx. 190 V
400 V class: Stops when DC bus voltage falls below approx. 380 V

Heatsink Overheat
Protection

Thermistor

Stall Prevention

Stall Prevention is available during acceleration, and during run.

Ground Protection

Electronic circuit protection

<3>

DC Bus Charge LED

Remains lit until DC bus voltage falls below 50 V