E2: Motor Parameters
E1-04
(303H)
Maximum Output Frequency
To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this
case, the setting for E1-08 will be disregarded. Ensure that the five frequencies
are set according to these rules:
E1-09
≤ E1-07 < E1-06 ≤ Ε1−11 ≤ E1-04
Note that if E1-11 = 0, then both E1-11 and E1-12 are disabled, and the above
conditions do not apply.
Note: Some parameters may not be available depending on the control mode.
• E1-07, E1-08 and E-10 are available only in the V/f control and Open Loop
Vector control modes.
• E1-11, E1-12 and E-13 are available only in the V/f control and Closed Loop
Vector control modes.
Default:
Max: 200.0 Hz
E1-05
(304H)
Maximum Voltage
Default: 230.0 V
Min: 0.0 V
Max: 255.0 V
E1-06
(305H)
Base Frequency
Default:
Min: 0.0 Hz
Max: 200.0 Hz
E1-07
(306H)
Middle Output Frequency
Default: 3.0 Hz
Min: 0.0 Hz
Max: 200.0 Hz
E1-08
(307H)
Middle Output Frequency
Voltage
Default:
Min: 0.0 V
Max: 255.0 V
E1-09
(308H)
Minimum Output Frequency
Default:
Min: 0.0 Hz
Max: 200.0 Hz
E1-10
(309H)
Minimum Output Frequency
Voltage
Default:
Min: 0.0 V
Max: 255.0 V
E1-11
(30AH)
Middle Output Frequency 2
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
E1-12
(30BH)
Middle Output Frequency Voltage 2
Default: 0.0 V
Min: 0.0 V
Max: 255.0 V
E1-13
(30CH)
Base Voltage
Default: 0.0 V
Min: 0.0 V
Max: 255.0 V
<2> Default setting is dependent on the control mode (A1-02) and the drive model (o2-04).
<5> Default setting is determined by the control mode (A1-02).
<9> Values shown here are for 200 V class drives. The default is 400 V when using a 400 V class drive.
<11> Parameter is ignored when E1-11 and E1-12 are set to 0.0.
<13> When E1-13 (Base Voltage) is set to 0.0, output voltage is controlled with E1-05 (Maximum Voltage) = E1-13. When Auto-Tuning is
performed, E1-05 and E1-13 are automatically set to the same value.
<23> Setting range depends on the type of motor being used. CLV allows a setting range of 10.0 to 120.0 Hz, while CLV/PM allows a setting range
of 4.0 to 120.0 Hz.
No.(Addr.)
Name
Description
Setting
E2-01
(30EH)
Motor Rated Current
Sets the motor nameplate full load current in Amps. Automatically set during
Auto-Tuning.
Default:
Min: 10% of drive
rated current
Max: 200% of drive
rated current
E2-02
(30FH)
Motor Rated Slip
Sets the motor rated slip. Automatically set during Auto-Tuning.
Default:
Min: 0.00 Hz
Max: 20.00 Hz
E2-03
(310H)
Motor No-Load Current
Sets the no-load current for the motor. Automatically set during Auto-Tuning.
Default:
Min: 0 A
Max: E2-01
E2-04
(311H)
Number of Motor Poles
Sets the number of motor poles. Automatically set during Auto-Tuning.
Default: 4
Min: 2
Max: 48
E2-05
(312H)
Motor Line-to-Line
Resistance
Sets the phase-to-phase motor resistance. Automatically set during Auto-Tuning.
Default:
Min: 0.000
Ω
Max: 65.000
Ω
No.(Addr.)
Name
Description
Setting
All Modes
common
_
Output Voltage (V)
Frequency (Hz)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
CLV
CLV/PM
V/f
OLV
common
_