Model number, Yea_common, 1 receiving – Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 16
1 Receiving
16
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
■
Model Number
<1> Drives with these specifications do not guarantee complete protection for the environmental conditions
indicated.
Table 1 Model Number and Specifications
Figure 4
Three-Phase 200 V
Three-Phase 400 V
No.
Max. Motor Capacity
kW (HP)
3 minute 50% Duty
Rated Output
Current A
No.
Max. Motor Capacity
kW (HP)
3 minute 50% Duty
Rated Output
Current A
2A0018
3.7 (5)
17.5
4A0009
3.7 (5)
9.0
2A0022
5.5 (7.5)
21.9
4A0012
5.5 (7.5)
11.5
2A0031
7.5 (10.0)
31.3
4A0019
7.5 (10.0)
18.5
2A0041
11.0 (15.0)
41.3
4A0023
11.0 (15.0)
22.5
2A0059
15.0 (20.0)
58.8
4A0030
15.0 (20.0)
30.0
2A0075
18.5 (25.0)
75.0
4A0039
18.5 (25.0)
38.8
2A0094
22.0 (30.0)
93.8
4A0049
22.0 (30.0)
48.8
2A0106
30.0 (40.0)
106.3
4A0056
30.0 (40.0)
56.3
2A0144
37.0 (50.0)
143.8
4A0075
37.0 (50.0)
75.0
2A0181
45.0 (60.0)
181.3
4A0094
45.0 (60.0)
93.8
2A0225
55.0 (75.0)
225.0
4A0114
55.0 (75.0)
113.8
2A0269
75.0 (100.0)
268.8
4A0140
75.0 (100.0)
140.0
2A0354
90.0 (125.0)
353.8
4A0188
90.0 (125.0)
187.5
2A0432
110.0 (150.0)
432.5
4A0225
110.0 (150.0)
225.0
-
-
-
4A0260
132.0 (175.0)
260.0
CIMR - L E 2
A
0018
D
A
C
Drive
L1000
Series
No. Enclosure Type
Design
Revision
Order
No.
Customized
Specifications
A
Standard model
No.
Region
Code
IP00
D
IP00 with top
protective cover
A
South
America
No.
Voltage Class
No.
Environmental
Specification
A
Standard
3-phase, 380-480 Vac
3-phase, 200-240 Vac
2
4
<1>
E
YEA_common
Refer to