B Parameter Table

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

193

Pa

ra

me

te

r T

abl

e

B

L8-07

(4B3H)

Output Phase Loss Protection
Selection

0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
3: Enabled (triggered at phase loss at start or when two phases lost mid-
operation)

<3>

Output phase loss fault (LF) is triggered when the output current falls below 5%
of the drive rated output current.
Output phase loss fault can mistakenly be triggered if the motor's rated current is
very small compared to the drive rating. Disable this parameter in such cases.

Default: 0
Min: 0
Max: 3

L8-09

(4B5H)

Output Ground Fault
Detection Selection

0: Disabled
1: Enabled

Default: 1
Min: 0
Max: 1

L8-10

(4B6H)

Heatsink Cooling Fan
Operation Selection

0: Run with timer (Fan operates only during run and for L8-11 seconds after
stop.)
1: Run always (Cooling fan operates whenever the drive is powered up.)
2: Temperature controlled (Cooling fan operated depending on the temperature
of the drives heatsink.)

Default: 0
Min: 0
Max: 2

L8-11

(4B7H)

Heatsink Cooling Fan Off
Delay Time

Sets a delay time to shut off the cooling fan after the Up/Down command is
removed when
L8-10 = 0.

Default: 60 s
Min: 0 s
Max: 300 s

L8-12

(4B8H)

Ambient Temperature Setting

Enter the ambient temperature. This value adjusts the oL2 detection level.

Default: 40

°C

Min: -10

°C

Max: 50

°C

L8-15

(4BBH)

oL2 (drive overload)
Characteristics Selection at
Low Speeds

0: No oL2 level reduction below 6 Hz.
1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz.

Default: 1
Min: 0
Max: 1

L8-27

(4DDH)

Overcurrent Detection Gain

Sets the gain for overcurrent detection as a percentage of the motor rated current.
Overcurrent is detected using the drive’s overcurrent level or the value set to L8-
27, whichever is lower.

Default: 300.0%
Min: 0.0%
Max: 300.0%

L8-29

(4DFH)

Current Unbalance Detection
(LF2)

0: Disabled
1: Enabled

Default: 1
Min: 0
Max: 1

L8-35

(4ECH)

<4>

Installation Selection

0: IP00 enclosure drive
2: IP00 enclosure drive with top protective cover

Default:

<1>

Min: 0
Max: 2

L8-38

(4EFH)

Automatic Torque Boost
Selection

Torque Boost increases the output current limit while decreasing the carrier
frequency when the output current exceeds a certain value.
0: Disabled
3: Enabled

Default: 0
Min: 0
Max: 3

L8-39

(4F0H)

Reduced Carrier Frequency

Sets the reduced carrier frequency used by the Torque Boost function.

Default: 3.0 kHz
Min: 1.0 kHz
Max: 15.0 kHz

L8-55

(45FH)

Internal Braking Transistor
Protection

0: Disabled. L8-55 should be disabled when using a regen converter or an
optional braking unit.
1: Protection enabled.

Default: 1
Min: 0
Max: 1

No.

(Addr.)

Name

Description

Setting

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

common

_

CLV

CLV/PM

V/f

OLV

common

_

CLV

CLV/PM

V/f

OLV

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_