4 Start-Up Programming
110
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
Wiring for CIMR-LE2A0269 to 2A0432, 4A0188 to 4A0260
• Voltage lower than 48 to 190 Vdc for 200 V class drives, 48 to 380 Vdc for 400 V class drives.
Figure 53
Figure 60 Voltage Lower Than 48 to 190 Vdc for 200 V Class Drives, 48 to 380 Vdc for 400 V Class Drives
<1> Install the inrush current suppression circuit outside the drive if the DC bus battery voltage is lower than 190 Vdc for 200 V class drives
and 380 Vdc for 400 V class drives. Failure to comply will cause the soft-charge bypass relay to remain open and result in damage to the
drive.
+
Current
sensor
R/L1
S/L2
T/L3
+1
−
U/T1
V/T2
W/T3
Relay
Power
supply
board
Control
board
OPE
CN19
(A)
(C)
(B)
Battery for control circuit
200 V Class: 250 to 340 Vdc
400 V Class: 500 to 680 Vdc
DC bus
power supply
H1-
= 55
(Rescue Operation)
L1
L2
L3
(D)
+3
Battery for DC bus
200 V Class: 48 to 190 Vdc
400 V Class: 48 to 380 Vdc
L1000A
After the DC bus voltage falls lower
than the battery voltage
0.5 s
After the DC bus voltage is charged
to the battery voltage
Magnetic Contactor B
Magnetic Contactor A
Magnetic Contactor C
Magnetic Contactor D
Magnetic Contactor Sequence
H1-
= 55
(Rescue Operation)
S
3
to S
12
SC
Inrush current
suppression circuit
<1>
Inrush current suppression resistor
YEA_comm