YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

Table 46 Connecting the PG Encoder Cable Specification

Table 47 PG Encoder Cable Types

Connecting PG-X3 Option

Parameter Settings and Connections for Different Encoder Types

• Connecting a Single-Pulse Encoder

When using a single-pulse encoder in V/f with PG control mode, connect the pulse output from the PG to the option and
set drive parameter F1-21 to 0.

• Connecting a Two-Pulse Encoder

When using a two-pulse encoder, connect the A and B pulse outputs on the PG to the option and set F1-21 to 1.
When using a two-pulse encoder in Closed Loop Vector control mode, connect pulse outputs A and B from the encoder
to the corresponding terminals on the option.

• Connecting a Two-Pulse Encoder with Z Marker Pulse

When using a two-pulse encoder with Z marker pulse, connect the A, B, and Z pulse outputs to the corresponding
terminals on the option.
When using a two-pulse encoder in CLV/PM control mode, connect pulse outputs A and B from the encoder to the
corresponding terminals on the option.

Option Terminal

PG Encoder Cable

Wire

Color

Pin

IP

1

Blue

C

IG

2

White

H

A+

3

Yellow

B

A–

4

White

G

B+

5

Green

A

B–

6

White

F

FE

E

N/A (shield)

D

Length

Type

Length

Type

10 m (32 ft.)

W5010

50 m (164 ft.)

W5050

30 m (98 ft.)

W5030

100 m (328 ft.)

W5100

Control Method

V/f with PG

Closed Loop Vector

No. of Encoders

1 (CN5-C)

2 (CN5-B)

1 (CN5-C)

2 (CN5-B)

Single Pulse (A)

F1-21 = 0

F1-37 = 0

N/A

N/A

Two Pulse (AB Quadrature)

F1-21 = 1

F1-37 = 1

No setting required

No setting required

Two Pulse with Marker (ABZ)

F1-21 = 1

F1-37 = 1

No setting required

No setting required