B Parameter Table

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

179

Pa

ra

me

te

r T

abl

e

B

F5: Digital Output Card (DO-A3)

F6: Communication Option Card

For more details on a specific option card, refer to the instruction manual for the option card.

No.(Addr.)

Name

Description

Setting

F5-01

(399H)

Terminal P1-PC Output
Selection

Sets the function for contact output terminals M1-M2, M3-M4, and photocoupler
output terminals P1 through P6.

Default: 0
Min: 0
Max: 161

F5-02

(39AH)

Terminal P2-PC Output
Selection

Default: 1
Min: 0
Max: 161

F5-03

(39BH)

Terminal P3-PC Output
Selection

Default: 2
Min: 0
Max: 161

F5-04

(39CH)

Terminal P4-PC Output
Selection

Default: 4
Min: 0
Max: 161

F5-05

(39DH)

Terminal P5-PC Output
Selection

Default: 6
Min: 0
Max: 161

F5-06

(39EH)

Terminal P6-PC Output
Selection

Default: 37
Min: 0
Max: 161

F5-07

(39FH)

Terminal M1-M2 Output
Selection

Default: F
Min: 0
Max: 161

F5-08

(3A0H)

Terminal M3-M4 Output
Selection

Default: F
Min: 0
Max: 161

F5-09

(3A1H)

DO-A3 Output Mode
Selection

0: Output terminals are each assigned separate output functions.
1: Binary code output
2: Use output terminal functions selected by parameters F5-01 through F5-08.

Default: 0
Min: 0
Max: 2

No.(Addr.)

Name

Description

Setting

F6-01

(3A2H)

Operation Selection after
Communications Error

0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.

Default: 1
Min: 0
Max: 3

F6-02

(3A3H)

External Fault from
Communication Option
Detection Selection

0: Always detected
1: Detection during run only

Default: 0
Min: 0
Max: 1

F6-03

(3A4H)

External Fault from
Communication Option
Operation Selection

0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.

Default: 1
Min: 0
Max: 3

F6-04

(3A5H)

bUS Error Detection Time

Sets the delay time for error detection if a bus error occurs.

Default: 2.0 s
Min: 0.0 s
Max: 5.0 s

F6-06

(3A7H)

Torque Limit Selection from
Communications Option

0: Disabled. Torque limit from option card disabled.
1: Enabled. Torque limit from option card enabled.

Default: 0
Min: 0
Max: 1

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

common

_

CLV

CLV/PM

V/f

OLV