T2-06: PM Motor Rated Current
Enter the PM motor rated current in amps.
T2-08: Number of PM Motor Poles
Enter the number of motor poles.
T2-09: PM Motor Base Speed
Enter the motor rated speed in r/min.
Note: T2-09 will be displayed when in CLV/PM.
T2-10: PM Motor Stator Resistance
Enter the motor stator resistance per motor phase.
T2-11: PM Motor d-Axis Inductance
Enter the d axis inductance per motor phase.
T2-12: PM Motor q-Axis Inductance
Enter the q axis inductance per motor phase.
T2-13: Induced Voltage Constant Unit Selection
Selects the units used for setting the induced voltage coefficient.
Setting 0: mV (r/min)
Setting 1: mV (rad/sec)
Note: If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2), and will automatically set E5-09 (Motor
Induction Voltage Constant 1) to 0.0. If T2-13 is set to 1, then the drive will use E5-09 and will automatically set E5-24 to 0.0.
No.
Parameter Name
Setting Range
Default
T2-06
PM Motor Rated Current
10% to 200% of the drive
rated current.
Depending on o2-04
No.
<1> When PG-E3 option connected: Max setting = 48
Parameter Name
Setting Range
Default
T2-08
Number of PM Motor Poles
2 to 120
6
No.
Parameter Name
Setting Range
Default
T2-09
PM Motor Base Speed
0 to 24000 r/min
150 r/min
No.
Parameter Name
Setting Range
Default
T2-10
PM Motor Stator Resistance
0.000 to 65.000
Ω
–
No.
Parameter Name
Setting Range
Default
T2-11
PM Motor d-Axis Inductance
0.00 to 600.00 mH
–
No.
Parameter Name
Setting Range
Default
T2-12
PM Motor q-Axis Inductance
0.00 to 600.00 mH
–
No.
Parameter Name
Setting Range
Default
T2-13
Induced Voltage Constant Unit Selection
0, 1
1