Table 57 – Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 222
C Standards Compliance
222
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum
allowable temperature of 75
°C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 40°C.
Table 57 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
2A0269
R/L1, S/L2, T/L3
95
× 2P
(3/0
× 2P)
95 to 150
(3/0 to 300)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
95
× 2P
(3/0
× 2P)
95 to 150
(3/0 to 300)
–, +1
–
95 to 150
(3/0 to 300)
+3
–
35 to 150
(2 to 300)
M10
18 to 23
(159 to 204)
35
(3)
35 to 150
(2 to 300)
M12
32 to 40
(283 to 354)
2A0354
R/L1, S/L2, T/L3
120
× 2P
(4/0
× 2P)
95 to 150
(3/0 to 300)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
120
× 2P
(4/0
× 2P)
95 to 150
(3/0 to 300)
–, +1
–
95 to 150
(3/0 to 300)
+3
–
95 to 150
(3/0 to 300)
M10
18 to 23
(159 to 204)
35
(2)
35 to 150
(2 to 300)
M12
32 to 40
(283 to 354)
2A0432
R/L1, S/L2, T/L3
150
× 2P
(250
× 2P)
95 to 300
(4/0 to 600)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
185
× 2P
(300
× 2P)
95 to 300
(4/0 to 600)
–, +1
–
120 to 300
(250 to 600)
+3
–
70 to 300
(3/0 to 600)
M10
18 to 23
(159 to 204)
50
(1)
120 to 240
(1 to 350)
M12
32 to 40
(283 to 354)
Drive Model
Terminal
Recommended
Wire Size
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N•m (lb.in.)
4A0009
R/L1, S/L2, T/L3
2.5
(14)
2.5 to 6.0
(14 to 10)
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
2.5
(14)
2.5 to 6.0
(14 to 10)
–, +1, +2
–
2.5 to 6.0
(14 to 10)
B1, B2
–
2.5 to 6.0
(14 to 10)
6.0
(10)
2.5 to 6.0
(14 to 10)
Drive Model
Terminal
Recommended
Wire Size
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N•m (lb.in.)