beautypg.com

Comtech EF Data CDM-760 User Manual

Page 102

background image

Front Panel Operation

Revision 2

CDM-760 Advanced High-Speed Trunking Modem

MN-CDM760

6–16

In MEO (Medium Earth Orbit satellite ) operating mode, the rate at which a message is

processed and the modem acts on the message, is 1X/250 ms. This takes into account the

lower round trip delay.

If the comparison of actual and target Eb/No yields a result that requires a change in output

power, the first correction made will be 80% of the calculated step, up to a maximum

change of 1 dB/message (1X/second in Normal Mode and up to 4X/second in MEO Mode).

This avoids the possibility of overshoot. Subsequent corrections are made until the

difference is less than 0.5 dB. At this point, the output power is only changed in increments

of 0.1 dB, to avoid ‘hunting’ around the correct set point.

The maximum change per message (1X/second in GEO mode and 1X/250 ms in

MEO Mode) will be 1 dB. Any request for more than 1 dB of power delta will

take more than one update period to perform. This is to keep the demodulator

from unlocking due to an instantaneous power change.

AUPC and ACM: AUPC and ACM operate autonomously:

AUPC drives the modem to a Tx power level that meets the target Es/No at the remote site.

ACM transmits the “best fit” MODCOD for the current Es/No.

Because AUPC and ACM function independently, there should be no reason to link them, as one

does not affect the other. In fact, run independently, each feature safeguards the other’s

function from a loss of lock.

(CONFIG: Tx) Power AUPC Target

This is the Target Es/No value that you wish to keep constant at the remote modem. Use

the  arrow keys to set the value. Press ENTER. Valid settings are:

Range

Step Size

Minimum

Maximum

0.0 dB

23.5 dB

0.1 dB

If the current Es/No exceeds this value, the AUPC control decreases the local modem’s

Tx output power but never drops below the configured Nominal value.

If the far side modem’s Es/No falls below this value, the AUPC control increases the local

modem’s Tx output power but never exceeds the Nominal value + Range.

For example: When you set the Nominal value to -25.0 dBm and the Range value to

03.0 dBm, then the maximum Tx power that AUPC drives the modem to will be -22

dBm.