Rockwell Automation 2711E-xxxx User Manual PanelView 1000e, 1200e 1400e User Manual
Page 74
![background image](/manuals/580215/74/background.png)
4–7
Installing PanelView 1400e Terminals
Publication 2711E-6.17 – November 1998
Figure 4.5 Stud-Mount Keypad Terminal Panel Cutout
4.350
"
(110.5 mm)
12.850
"
(326.4 mm)
PANEL CUT–OUT LAYOUT
1.500
"
(38.1 mm)
5.500
"
(139.7 mm)
5.500
"
(139.7 mm)
6.425
"
(163.2 mm)
8.450
"
(214.6 mm)
8.700
"
(221.0 mm)
9.156
"
(232.6 mm)
6.985
"
(177.4 mm)
13.970
"
(354.8 mm)
∅
7/32
" 18 Holes Typ.
Bezel Border Line
6.700
"
(170.2 mm)
6.700
"
(170.2 mm)
4.350
"
(110.5 mm)
16.900
"
(429.3 mm) 8.700"
(221.0 mm)
19.00
"
(482.6 mm)
9.50
"
(241.3 mm)
8.700
"
(221.0 mm)
17.400
"
(442.0 mm)
9.156
"
(232.6 mm)
ЙЙЙЙЙЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙЙЙЙЙЙ
PANEL CUT–OUT LAYOUT
CL
CL
1.500
"
(38.1 mm)
24721b
Mounting Your PanelView 1400e Terminal in a 19-inch Rack
You can mount a PanelView 1400e Stud-Mount Keypad terminal in a
standard EIA 19-inch rack. No additional hardware is required.
To mount the terminal:
1. Place the terminal in the rack, aligning the studs with the holes in
the rack.
2. Insert the terminal until the gasket material is flush with the wall
cutout or panel.
3. Nuts are provided with the stud-mount terminal models. Tighten
the nuts to compress the gasket on the terminal.
Built-in spacers prevent the gasket from being over-compressed. The
tightening torque increases significantly when you reach the correct
compression. At this point the tightening torque should not exceed
10 inch-pounds.
To mount a PanelView 1400e Stud-Mount Touch Screen terminal in
a standard 19-inch EIA rack, you require a Rack Mount Kit (Catalog
No. 2711-NR4).