Specifications: 1200e Operator Terminal

B–6

Publication 2711E-6.17 – November 1998

The following table provides details of the ac power specifications:

Power Supply Type

Switching

Range

90 – 132, 180 – 264 Vac
automatic setting by the PanelView 1200e terminal to
match available power supply

Frequency Range

47 – 63 Hz

Power Consumption

Color terminal

65 W typical
90 W maximum

Volt Amps

Color terminal

160 VA typical
220 VA maximum

While the color terminal degausses, there is a 5.5-amp surge at
115 volts. At 230 volts, there is an 11-amp surge. The surge lasts less
than 400 milliseconds. Automatic degauss occurs each time ac power
is re-applied to the unit and at midnight (according to the terminal
system clock) daily.

PanelView 1200e terminals:

Require one fuse for each ac line

Have fuses that the user can access from the rear of the terminal

Accept either US or European fuse types

US fuse: BUSS AGC-3, 3 amps, 250 Vac, 1/4–inch

×

1-1/4–inch

European fuse: BUSS GDB-3, 3 amps, 250 Vac, 5 mm

×

20 mm

!

ATTENTION: Fuses must be replaced by authorized
service personnel only. PanelView 1200e terminals
contain neutral fuses. Disconnect power before
servicing the unit.

PanelView 1200e terminals support the IBM character set for alarm,
local, and information messages.

The PanelView 1200e terminal supports:

256K of flash memory for application file

PCMCIA card slot of variable size (256K bytes to 16 MB—depends
on user application file)

RAM tests and Memory Checksum tests can be initiated from the
Terminal Diagnostics screen in Configuration mode.

AC Power

Fuses

Character Set

User Memory