beautypg.com

Keyboard and bar code reader support, Ac power, Fuses – Rockwell Automation 2711E-xxxx User Manual PanelView 1000e, 1200e 1400e User Manual

Page 186

background image

Specifications: 1400e Operator Terminal

C–7

Publication 2711E-6.17 – November 1998

Following are the keyboards supported by the PanelView 1400e
terminal.

Manufacturer

Part Number

Allen-Bradley

6189-KBM1

Allen-Bradley

6189-KBD1

Allen-Bradley

6189-KBE1

Following is the bar code reader supported by the PanelView 1400e
terminal.

Manufacturer

Part Number

Allen-Bradley

2755HDG4 Series A, Revision C

Following are the ac power specifications for the PanelView 1400e
terminal.

Power Supply Type

Switching

Range

90–132, 180–264 V ac
automatic setting by the PanelView 1400e terminal to
match available power supply

Frequency Range

47–63 Hz

Power Consumption

Color terminal

75 W typical
100 W maximum

Volt Amps

Color terminal

180 VA typical
240 VA maximum

While the color terminal degausses, there is a 5.5-amp surge at
115 volts. At 230 V, there is an 11-amp surge that lasts less than
400 milliseconds. Automatic degauss occurs every time ac power is
re-applied to the terminal.

PanelView 1400e terminals:

Require one fuse for each ac line

Have fuses the user can access from the rear of the terminal

Accepts the following fuse type: BUSS GDC-3.15, 3.15 A,
250 V ac, 5 mm

×

20 mm

!

ATTENTION: Fuses must be replaced by authorized
service personnel only. PanelView 1400e terminals
contain neutral fuses. Disconnect power before
servicing the unit.

Keyboard and Bar Code
Reader Support

AC Power

Fuses