Specifications: 1400e Operator Terminal
C–7
Publication 2711E-6.17 – November 1998
Following are the keyboards supported by the PanelView 1400e
terminal.
Manufacturer
Part Number
Allen-Bradley
6189-KBM1
Allen-Bradley
6189-KBD1
Allen-Bradley
6189-KBE1
Following is the bar code reader supported by the PanelView 1400e
terminal.
Manufacturer
Part Number
Allen-Bradley
2755HDG4 Series A, Revision C
Following are the ac power specifications for the PanelView 1400e
terminal.
Power Supply Type
Switching
Range
90–132, 180–264 V ac
automatic setting by the PanelView 1400e terminal to
match available power supply
Frequency Range
47–63 Hz
Power Consumption
Color terminal
75 W typical
100 W maximum
Volt Amps
Color terminal
180 VA typical
240 VA maximum
While the color terminal degausses, there is a 5.5-amp surge at
115 volts. At 230 V, there is an 11-amp surge that lasts less than
400 milliseconds. Automatic degauss occurs every time ac power is
re-applied to the terminal.
PanelView 1400e terminals:
•
Require one fuse for each ac line
•
Have fuses the user can access from the rear of the terminal
•
Accepts the following fuse type: BUSS GDC-3.15, 3.15 A,
250 V ac, 5 mm
×
20 mm
!
ATTENTION: Fuses must be replaced by authorized
service personnel only. PanelView 1400e terminals
contain neutral fuses. Disconnect power before
servicing the unit.
Keyboard and Bar Code
Reader Support
AC Power