Application startup – Rockwell Automation 2711E-xxxx User Manual PanelView 1000e, 1200e 1400e User Manual
Page 110

5–26
Configuring PanelView Terminals
Publication 2711E-6.17 – November 1998
The initial values of certain multistate input control objects such as
Control Selectors, Interlocked Push Buttons, and Numeric Input
objects can be assigned in PanelBuilder 1400e software. These
values are PLC input states that are initially transferred to the PLC
depending on the operation chosen in the Application Startup screen.
Note: All objects (tags) have initial values. Some objects have
initial states and the values associated with these states override the
initial values for these objects.
To view application start-up settings:
"
In the Terminal Configuration screen, choose the Application
Startup button to display the following screen.
Start-up Options Over Remote I/O and ControlNet (Scheduled)
By default, when an application is downloaded or made current and
the terminal is switched to Run mode, the first values written to the
PLC are the initial values. Also, after a power cycle, the initial value
or initial states values are written. When the terminal is switched
from Run to Configure to Run mode, the last state value is written.
If you choose No for Use Default Operation, the initial values or
state values are written when the terminal is in Run mode for the first
time. After a power cycle, or when switched between modes, the last
state value is written. When the terminal is switched from Run to
Configure to Run mode, the last state value is written. The default is
Yes for Use Default Operation.
When the terminal is switched from Run to Configure mode, nothing
is written.
Application Startup
"