beautypg.com

Rockwell Automation 2711E-xxxx User Manual PanelView 1000e, 1200e 1400e User Manual

Page 31

background image

1–18

Introducing the PanelView Terminals

Publication 2711E-6.17 – November 1998

Figure 1.4 KTCx and KTCs Switch Settings — Base I/O
Address

Base I/O Address 220

up (1)

down (0)

1 2 3 4

For more information, see the documentation that comes with the
KTCx or KTCs card.

For more information about communication devices for ControlNet,
see the PanelBuilder 1400e Configuration Software for Windows
User Manual
, A-B publication 2711E-819.

When you switch from Configure to Run mode to execute
ControlNet applications, you may notice a delay of 5 to 15 seconds.
During this time, the message “Initializing Communications”
appears on the screen. The delay occurs because the KTCx or KTCs
card has a separate processor that takes 5 to 15 seconds to
synchronize with ControlNet. When you switch to Run mode the
application screen will appear after approximately 5 seconds. Then
the message “Communication Lost” will appear for approximately
10 seconds, while the connection is established.

The following host controllers can be connected to the terminals over
ControlNet.

Logix55xx

You can connect one or more terminals to a 1756-CNET ControlNet
Communications Module.

PLC-5/20C, 5/40C, 5/60C, 5/80C

You can connect the PanelView terminal to the PLC-5C enhanced
family of programmable controllers over ControlNet release 1.25.

PLC-5/20C15, 5/40C15, 5/60C15, 5/80C15

You can connect the PanelView terminal to the PLC-5C15 enhanced
family of programmable controllers over ControlNet release 1.5.