Specifications: 1000e Operator Terminal

A–6

Publication 2711E-6.17 – November 1998

Up to 64 block transfer files can be configured, with up to 64
words for each file. Files can be configured as read or write files
in any combination.

Total Block Transfer bits possible: 64 files

×

64 word/file

×

16 bit/word in any input/output combination

Application files can be uploaded and downloaded by the PLC-5
or SLC 5/04 Pass-Through feature

The RS-232 serial communications port can be connected to either
the development system for uploading/downloading application files,
or to a printer for printing screen images, alarm history and alarm
status reports, or alarm messages. Separate port settings can be
assigned for each of these purposes. The applicable printer port
settings are used automatically and are as follows, with the default in
brackets:

Baud Rates

300,1200, 2400, 4800, 9600, 19.2 kilobaud (9600)

Parity Types

Odd, Even, None (None)

Stop Bits

1, 2 (1)

Data Bits

7, 8 (8)

Handshake

Hardware, Software (X-ON, X-OFF), None (Software)

Auto Line Feed

Off, On (On)

Auto Form Feed

Off, On (On)

The factory defaults for file transfer are the same as the default
settings the development software will apply to the selected RS-232
port on your development system, so you don’t normally need to
change them.

File transfer settings are separate from the printer and are as follows:

Baud Rates

300,1200, 2400, 9600, 19200 (9600)

Parity Types

Even, None (None)

Error

CRC, BCC (BCC)

Serial Communications
Port