To connect power to the terminal:

1. Prepare the power wires by stripping the wire of its protective

coating to a length of

½ to ¾ of an inch (1 to 2 cm).

2. Turn the screw on the power connector counter-clockwise to open

the wire slot. Insert the wire fully into its appropriate slot.

3. Turn the screw clockwise until the wire is held firmly in place.

4. Repeat the procedure until all three power wires are connected.

Figure 2.10 The Power Connector

20164

L1 ~ (Vac)

L2N ~ (Vac)

L1

L2

GND

(Protective Earth)

Connecting the Upload/Download Cable

The RS-232 port connects the terminal to the host computer for
uploading and downloading application files using the RS-232 serial
cable (Upload/Download cable). Cables of different lengths are
available in separate kits (A-B Catalog Numbers 2711-NC13,
2711-NC14, 2706-NC13).

The Upload/Download cable can be connected to a computer with a
9-pin, RS-232 port (IBM PC AT

®-type computers). Use the cable

pinout shown in Figure 2.11 to connect the terminal to the host
computer. For instructions about transferring files using the
Upload/Download cable, refer to the PanelBuilder 1400e
Configuration Software for Windows User Manual