2–16

Installing PanelView 1000e Terminals

Publication 2711E-6.17 – November 1998

To connect the PanelView 1000e terminal to the DH+

network:

1. Remove the Remote I/O and DH+ connector plug from the rear of

the terminal.

2. Turn terminal screws 2 and 1 on the connector counter-clockwise.

See Figure 2.15 for plug connection locations.

3. Connect the clear wire to plug terminal 1 and the blue wire to

plug terminal 2. Connect shield and shield drain wire to middle
plug terminal. Tighten the screws to secure the wires.

4. Re-insert the plug into the terminal connector.

Note: If the terminal is the last device on the link, connect a

½ watt

terminating resistor across terminals 1 and 2. The value of the
resistor depends on the DH+ baud rate:

for 57.6 kilobaud and 115.2 kilobaud, use a 150-ohm resistor
(A-B Part Number 740018-29)

for 230 kilobaud, use an 82-ohm resistor (A-B Part Number
740018-23)

To connect the PanelView 1000e terminal to the ControlNet network:

The PanelView 1000e terminal (A-B Catalog Number 2711E-T10C6
and 2711E-K10C6) requires an enhancement with a 1784-KTCX,
1784-KTCX15, or 1784-KTCS card and 2711E-NA2 adapter. You
can use the ControlNet-enhanced PanelView 1000e terminals (A-B
Catalog Number 2711E-T10C7, 2711E-T10C15, 2711E-K10C7, and
2711E-K10C15).

"

Connect a PanelView Terminal to a ControlNet network via a tap
with a 1-meter (39.4-inch) drop cable. Use any tap with one of
the following catalog numbers: 1786-TPS, 1786-TPYS,
1786-TPR, or 1786-TPYR. See the ControlNet PLC-5
Programmable Controllers User Manual
(A-B Publication
1785-6.5.14) for more information about ControlNet taps.

Note: ControlNet taps contain passive electronics and must be
purchased from Allen-Bradley for the network to operate correctly.

Note: If the terminal is the last device on the link, connect a 75-ohm,
1-watt terminating resistor to the unused connector on the tap (A-B
Catalog Number 1786-XT).

See the ControlNet PLC-5 Programmable Controllers User Manual
(A-B Publication 1785-6.5.14), the ControlNet Communication
Interface
Card (A-B Publication 1784-5.20), and the ControlNet
Planning and
Installation Manual (A-B Publication 1786-6.2.1) for
more information about ControlNet.

"

"

"