Installing PanelView 1200e Terminals

Publication 2711E-6.17 – November 1998

To connect the PanelView 1200e terminal over Remote I/O:

1. Remove the Remote I/O and DH+ connector plug from the rear of

the terminal. Figure 3.1 shows its location.

2. Turn terminal screws 2 and 1 on the connector counter-clockwise.

See Figure 3.15 for plug connection locations.

3. Connect the clear wire to plug terminal 2 and the blue wire to

plug terminal 1. Connect shield and shield drain wire to middle
plug terminal.

4. Tighten the screws to secure the wires.

5. Re-insert the plug into the terminal connector.

Note: If the terminal is the last device on the link, connect a 1/2 watt
terminating resistor across terminals 1 and 2. The value of the
resistor depends on the Remote I/O baud rate:

for 57.6 kilobaud and 115.2 kilobaud, use a 150-ohm resistor
(A-B Part Number 740018-29)

for 230 kilobaud, use an 82-ohm resistor (A-B Part Number
740018-23)

To connect the PanelView 1200e terminal to the DH+

network:

1. Remove the Remote I/O and DH+ connector plug from the rear of

the terminal. Figure 3.1 shows its location.

2. Turn terminal screws 2 and 1 on the connector counter-clockwise.

See Figure 3.15 for plug connection locations.

3. Connect the clear wire to plug terminal 1 and the blue wire to

plug terminal 2. Connect shield and shield drain wire to middle
plug terminal.

4. Tighten the screws to secure the wires.

5. Re-insert the plug into the terminal connector.

Note: If the terminal is the last device on the link, connect a 1/2 watt
terminating resistor across terminals 1 and 2. The value of the
resistor depends on the DH+ baud rate:

for 57.6 kilobaud and 115.2 kilobaud, use a 150-ohm resistor
(A-B Part Number 740018-29)

for 230 kilobaud, use an 82-ohm resistor (A-B Part Number
740018-23)

"

"