Fuses, Character set, User memory – Rockwell Automation 2711E-xxxx User Manual PanelView 1000e, 1200e 1400e User Manual
Page 168: Alarm relay, Batteries
Specifications: 1000e Operator Terminal
A–8
Publication 2711E-6.17 – November 1998
PanelView 1000e terminals:
•
require one fuse for each ac line
•
has fuses the user can not access
•
uses Littelfuse 218001, or equivalent, Type T, 1.0 A, 250 Vac,
5 mm
×
20 mm
!
ATTENTION: Fuses must be replaced by authorized
service personnel only. PanelView 1000e terminals
contain neutral fuses. Disconnect power before
servicing the unit.
PanelView 1000e terminals support the IBM character set for alarm,
local, and information messages.
PanelView 1000e terminals support:
•
2.25 MB of Flash memory for application file
•
PCMCIA card of variable size (depends on user application file),
256K to 16 MB
RAM tests and Memory Checksum tests can be initiated in the
Terminal Diagnostics screen in Configuration mode.
•
Form-C Contact
•
24 V ac Max, 1 amp continuous Max
•
24 V dc Max, 1 amp continuous Max
•
Minimum Voltage: 100 mV dc
•
Minimum Current: 10 mA dc
PanelView’s permanent, factory-installed lithium battery has a total
lithium weight of not more than 0.5 gram. The battery is not
burdened when ac power is applied to the terminal. The following
chart indicates battery life, with continuous exposure to the specified
temperatures, assuming ac power is applied to the terminal 8 hours a
day, 5 days a week. These calculations are based on battery life
specifications provided by the battery manufacturer and do not take
battery shelf life into account.
ББББББББ
ББББББББ
+86
°
F (+30
°
C)
ББББББББ
ББББББББ
7.7 years
ББББББББ
ББББББББ
+104
°
F (+40
°
C)
ББББББББ
ББББББББ
4.5 years
ББББББББ
ББББББББ
+113
°
F (+45
°
C)
ББББББББ
ББББББББ
3.8 years
ББББББББ
ББББББББ
+122
°
F (+50
°
C)
ББББББББ
ББББББББ
3.2 years
ББББББББ
ББББББББ
+140
°
F (+60
°
C)
ББББББББ
ББББББББ
2.5 years
Battery fail indications are displayed automatically.
Fuses
Character Set
User Memory
Alarm Relay
Batteries