2–26
Command Word/Bit Descriptions
Publication 1771-6.5.88 – July 1997
Notes: 1. For [ ] engineering units, see page 3.
2. When using the Inject/Clamp/Eject mode, all pressure readings are system pressure at input 2, except where noted.
Bit-mapped Control Words
Word
Bit
Description
EAC01
Block ID = 00010110 (Low byte). High byte reserved for the module Do not use.
EAC02
Configuration Selections
B00-B02
Selected Velocity Advance Control Valve
The module uses its algorithm to drive the following output during any advance stroke (Vel/Pos Ejector Profile).
B02 B01 B00
0 0 0 Output #1
0 0 1 Output #2
0 1 0 Output #3
0 1 1 Output #4
1 0 0 Output #5
1 0 1 Output #6
1 1 0 Output #7
1 1 1 Output #8
B03
Open
B04-B06
Selected Pressure Advance Control Valve
The module uses its algorithm to drive the following output during any advance stroke (Press/Pos Ejector Profile).
B06 B05 B04
0 0 0 Output #1
0 0 1 Output #2
0 1 0 Output #3
0 1 1 Output #4
1 0 0 Output #5
1 0 1 Output #6
1 1 0 Output #7
1 1 1 Output #8
B07
Pressure Algorithm Selection
= 0 Dependent Gains (ISA)
= 1 Independent Gains (A-B)
B08-B15
Open
EAC03 - 04
Open
Expert Response Compensation (ERC) Percentage
Word
Description
EAC05
Minimum Velocity-advance Control ERC Percentage [31] Although error coding allows range of 00000 to 09999, the module limits it
to a minimum of 01000.
EAC06
Minimum Pressure-advance Control ERC Percentage [31] Although error coding allows range of 00000 to 09999, the module limits
it to a minimum of 01000.
EAC07
Open
Watchdog Timer
Word
Description
EAC08
Full Profile Watchdog Timer Preset [21] When Module starts the Ejector Profile, it starts an internal Profile Watchdog Timer. It stops
this timer and resets its accumulated value to zero (after reporting total execution time in EPS57) when it completes the profile. It
sets master status bit SYS04-B14 when the accumulated value of this timer equals or exceeds this entry. A zero entry inhibits
SYS04-B14.
EAC – Ejector Advance
Configuration Block