2–71
Command Word/Bit Descriptions
Publication 1771-6.5.88 – July 1997
MCC
MCC27
Clamp Position Minimum Software Travel Limit [13] The module continuously compares real-time clamp position against this entry.
The module sets alarm status bit SYS07-B02 and forces all of its outputs to zero when executing a clamp close profile and clamp
position is less than or equals this entry. A zero entry inhibits SYS07-B02.
MCC28
Clamp Position Maximum Software Travel Limit[13] The module continuously compares real-time clamp position against this entry.
the module sets alarm status bit SYS07-B03 and forces all of its outputs to zero when executing a clamp open profile and clamp
position equals or exceeds this entry. A zero entry inhibits SYS07-B03.
MCC29
Clamp Software Travel Limit Alarm Deadband [17] After sensing a clamp overtravel and latching alarm status bit SYS07-B02 or
SYS07-B03, the module will not unlatch bit until real-time clamp position is inside the overtravel setpoint by an incremental length
equal to this entry. This incremental position will be added to MCC27 in order to determine the clamp position required to unlatch
SYS07-B02. This incremental position will be subtracted from MCC28 in order to determine the clamp position required to unlatch
SYS07-B03.
MCC30
Clamp Position Transducer Digital Filter [23] A non-zero entry forces the module to filter the input before using the result for all
clamp position calculations. Use this parameter to soften the input signal from a linear potentiometer.
Clamp Pressure Transducer Configuration
The module accesses data in MCC31-MCC36 if bit patterns in
MCC02 and MCC03 indicate that the module is connected to a
clamp pressure sensor.
Word
Description
MCC31
Minimum Clamp Pressure [02]
MCC32
Maximum Clamp Pressure [02]
MCC33
Analog Signal at Minimum Clamp Pressure [24]
MCC34
Analog Signal at Maximum Clamp Pressure [24]
MCC35
High Clamp Pressure Alarm Setpoint [02] The module continuously compares real-time clamp pressure against this entry. and sets
alarm status bit SYS05-B01 when clamp pressure equals or exceeds this entry. A zero entry inhibits SYS05-B01.
MCC36
Clamp Pressure Alarm Time Delay [23] Total time the module must monitor a continuous clamp pressure in excess of the non-
zero entry in all clamp pressure alarm setpoints before setting the associated alarm status bit. Setpoint/bit pairs affected are:
Setpoint
Alarm Status Bit
MCC35
SYS05-B01
JGC07
SYS05-B10
FCC57
SYS05-B12
SCC57
SYS05-B13
TCC57
SYS05-B14
LPC57
SYS05-B15
FOC57
SYS06-B09
SOC57
SYS06-B10
TOC57
SYS06-B11
OSC57
SYS06-B12
Use a non-zero entry in this word to filter out clamp pressure spikes of short enough duration to avoid nuisance alarms.
Ejector Position Transducer Configuration
The module accesses data in MCC37-MCC44 if bit patterns in
MCC02 and MCC03 indicate that the module is connected to an
ejector position sensor.
Word
Description
MCC37
Minimum Ejector Position [15]
MCC38
Maximum Ejector Position [15]
MCC39
Analog Signal at Minimum Ejector Position [24]
MCC40
Analog Signal at Maximum Ejector Position [24]
MCC41
Ejector Position Minimum Software Travel Limit [15] The module continuously compares real-time ejector position against this entry.
The module sets alarm status bit SYS07-B04 and forces all of its outputs to zero when executing an ejector retract profile and ejector
position is less than or equals this entry. A zero entry inhibits SYS07-B04.