Rockwell Automation 1771-QDC PLASTIC MOLD.MODULE User Manual
Page 139
2–73
Command Word/Bit Descriptions
Publication 1771-6.5.88 – July 1997
MCC
Cavity (or System) Pressure Transducer Configuration
The module accesses data in MCC57-MCC62 if bit patterns in MCC02
and MCC03 indicate that the module is connected to a cavity (or
system) pressure sensor. The data will refer to a system pressure sensor
at input #2 only if MCC02-B03, -B04, and -B05 are all SET.
Word
Description
MCC57
Minimum Cavity (or System) Pressure [04] or [01]
MCC58
Maximum Cavity (or System) Pressure [04] or [01]
MCC59
Analog Signal at Minimum Cavity (or System) Pressure [24]
MCC60
Analog Signal at Maximum Cavity (or System) Pressure [24]
MCC61
High Cavity (or System) Pressure Alarm Setpoint [04] or [01] The module continuously compares real-time cavity (or system) pressure
against this entry. The module sets alarm status bit SYS05-B04 when cavity (or system) pressure equals or exceeds this entry. A zero
entry inhibits SYS05-B04.
MCC62
High Cavity (or System) Pressure Alarm Time Delay [23] Total time the module must monitor a continuous cavity (or system) pressure
in excess of the non-zero entry in all cavity (or system) pressure alarm setpoints before setting the associated alarm status bit.
If bit patterns in MCC02 and MCC03 indicate that the module is connected to a cavity pressure sensor, setpoint/bit pairs affected are:
Setpoint
Alarm Status Bit
MCC61
SYS05-B04
INC58
SYS06-B01
PKC58
SYS06-B03
HDC58
SYS06-B05
If bit patterns in MCC02 and MCC03 indicate that the module is connected to a system pressure sensor, setpoint/bit pairs affected are:
Setpoint
Alarm Status Bit
MCC61
SYS05-B04
JGC06
SYS05-B09
JGC07
SYS05-B10
JGC08
SYS05-B11
FCC57
SYS05-B12
SCC57
SYS05-B13
TCC57
SYS05-B14
LPC57
SYS05-B15
INC57
SYS06-B00
PKC57
SYS06-B02
HDC57
SYS06-B04
PRC57
SYS06-B06
PLC57
SYS06-B07
PSC57
SYS06-B08
FOC57
SYS06-B09
SOC57
SYS06-B10
TOC57
SYS06-B11
OSC57
SYS06-B12
EAC57
SYS06-B13
Use a non-zero entry in this word to filter out cavity (or system) pressure spikes of short enough duration to avoid nuisance alarms.
MCC63
Reserved
MCC64
Number of Input Samples for Loss-of-sensor Alarms [29] Range of 0-200. The module monitors sensor inputs for out-of-range
signals. To avoid nuisance alarms caused by electrical noise, enter a non-zero value. When the module detects a number of
consecutive
out-of-range input scans (consecutive loss-of-sensor samples) equal to or greater than this value, it sets the
loss-of-sensor alarm. Setting to zero gives no protection against nuisance alarms.