2–67
Command Word/Bit Descriptions
Publication 1771-6.5.88 – July 1997
LPC
Word
Description
LPC33
Output #1 Set-output Value at End of Profile [19]
LPC34
Output #2 Set-output Value at End of Profile [19]
LPC35
Output #3 Set-output Value at End of Profile [19]
LPC36
Output #4 Set-output Value at End of Profile [19]
LPC37
Output #5 Set-output Value at End of Profile [19]
LPC38
Output #6 Set-output Value at End of Profile [19]
LPC39
Output #7 Set-output Value at End of Profile [19]
LPC40
Output #8 Set-output Value at End of Profile [19]
Pressure Control Limits
Word
Description
LPC41
Pressure Minimum Control Limit [02] Minimum controllable clamp pressure attainable during any Clamp Low Pressure Close Profi-
le. The module expects this clamp pressure when setting its selected valve to the %-output in LPC43.
LPC42
Pressure Maximum Control Limit [02] Maximum controllable clamp pressure attainable during any Clamp Low Pressure Close
Profile. The module expects this clamp pressure when setting its selected valve to the %-output in LPC44.
LPC43
Selected Pressure Valve Output of Minimum [19] 0% CV output percentage that the module uses to drive the selected pressure
valve during any Clamp Low Pressure Close Profile. The module expects a pressure equal to LPC41 when setting the selected
pressure valve to this %-output during profile execution. The Clamp Low Pressure Close Profile will be executed as a reverse-act-
ing algorithm if this entry is greater than LPC44.
LPC44
Selected Pressure Valve Output of Maximum [19] 100% CV output percentage that the module uses to drive the selected pressure
valve during any Clamp Low Pressure Close Profile. The module expects a pressure equal to LPC42 when setting the selected
pressure valve to this %-output during profile execution. The Clamp Low Pressure Close Profile will be executed as a reverse-act-
ing algorithm if this entry is less than LPC43.
LPC45 - 48
Open
Profile Tuning Constants
Word
Description
LPC49
Proportional Gain for Pressure Control [30]
LPC50
Integral Gain for Pressure Control [27] or [28]
LPC51
Derivative Gain for Pressure Control [26] or [21]
LPC52 - 56
Open
Profile Pressure Alarm Setpoint
Word
Description
LPC57
Profile High Pressure Alarm Setpoint [02] The module compares real-time clamp pressure against this entry when executing the
Clamp Low Pressure Close Profile. The module sets alarm status bit SYS05-B15 when clamp pressure equals or exceeds this
entry during the Clamp Low Pressure Close Profile. A zero entry inhibits SYS05-B15.
LPC58 - 64
Open