Cps - clamp close profiles status block, Cps – clamp close profiles status block – Rockwell Automation 1771-QDC PLASTIC MOLD.MODULE User Manual
Page 182
3–6
Status Word/Bit Descriptions
Publication 1771-6.5.88 – July 1997
Notes: 1. For [ ] engineering units, see page 3.
2. When using the Inject/Clamp/Eject mode, all pressure readings are system pressure at input 2, except where noted.
Word
Description
CLS37
Ejector Tip Advance Segment
CLS38
Reserved
CLS39
Ejector Full Retract Segment 1
CLS40
Ejector Full Retract Segment 2
CLS41
Ejector Full Retract Segment 3
CLS42
Reserved
CLS43 - 64
Open
Bit-mapped Status Words
Word
Bit
Description
CPS01
Block ID = 00000010 (Low byte). High byte identical to SYS01
CPS02
See SYS02
CPS03
See SYS03
CPS04
See SYS04
CPS05
Open
CPS06
Open
CPS07
CV High Limit Alarms
The module latches each bit when executing the subject profile segment in closed loop, and drives its algorithm CV to
maximum (100%) in an attempt to control the profile setpoint.
The module unlatches each bit when it completes execution of the subject profile segment in open loop, or in closed
loop without driving its algorithm CV to maximum (100%).
When this bit
is latched ON:
algorithm CV
is maximum during:
B00
Segment 1 (First Clamp Close)
B01
Segment 2 (First Clamp Close)
B02
Segment 3 (First Clamp Close)
B03
Segment 4 (Second Clamp Close)
B04
Segment 5 (Second Clamp Close)
B05
Segment 6 (Second Clamp Close)
B06
Segment 7 (Third Clamp Close)
B07
Segment 8 (Third Clamp Close)
B08
Segment 9 (Third Clamp Close)
B09
Segment 1 (Clamp Low Pressure Close)
B10
Segment 2 (Clamp Low Pressure Close)
B11-B15
Open
CPS08
CV Low Limit Alarms
The module latches each bit when executing the subject profile segment in closed loop, and drives its algorithm CV to
minimum (0%) in an attempt to control the profile setpoint.
The module unlatches each bit when it completes execution of the subject profile segment in open loop, or in closed
loop without driving its algorithm CV to minimum (0%).
When this bit
is latched ON:
algorithm CV
is maximum during:
B00
Segment 1 (First Clamp Close)
B01
Segment 2 (First Clamp Close)
B02
Segment 3 (First Clamp Close)
B03
Segment 4 (Second Clamp Close)
CPS – Clamp Close
Profiles Status Block