Rockwell Automation 1771-QDC PLASTIC MOLD.MODULE User Manual
Page 224
![background image](/manuals/579944/224/background.png)
3–48
Status Word/Bit Descriptions
Publication 1771-6.5.88 – July 1997
Notes: 1. For [ ] engineering units, see page 3.
2. When using the Inject/Clamp/Eject mode, all pressure readings are system pressure at input 2, except where noted.
Process Times
Word
Description
SYS57
Accumulated Tonnage Time [21]
If bit patterns in MCC02 and MCC03 indicate that the module is connected to a clamp pressure transducer, the module:
S
clears this word and starts tonnage watchdog timer when it completes Clamp LPC Profile and sets its outputs to LPC33 - 40
S
stops timer when it sets master status bit SYS03-B02 and reports accumulated value of timer (99.99 seconds max) in this word
S
sets master status bit SYS04-B15 when this value equals or exceeds LPC07. A zero entry in LPC07 inhibits SYS04-B15.
The module also resets this word to zero when it detects an F-to-T transition of DYC03-B00.
SYS58
Accumulated Cure Time [22]
If bit patterns in MCC02 and MCC03 indicate that the module is connected to a ram (screw) position transducer, the module:
At completion of the Hold Profile:
S
starts an internal cure timer
S
starts an internal cure timer
S
sets master status bit SYS03-B03
S
reports the accumulated time in this word
When the value in this word equals the cure timer preset (HPC6:
When the value in this word equals the cure timer reset (HPC6:
S
resets master status bit SYS03-B03
S
sets master status bit SYS03-B05
S
stops accumulating time in this word
When it receives an F-to-T transition of DYC03-B01
When it receives an F-to-T transition of DYC03-B01
S
resets master status bit SYS03-B03
S
resets master status bit SYS03-B05 resets this word to zero
If bit patterns in MCC02 and MCC03 indicate that the module is connected to both a ram (screw) position transducer and a clamp
position transducer the module also (when it receives an F to T transition of DYC02 B00 B01 B02 or B03):
position transducer, the module also (when it receives an F-to-T transition of DYC02-B00, -B01, -B02, or -B03):
S
resets master status bit SYS03-B03
S
resets master status bit SYS03-B05
S
resets this word to zero
SYS59
Accumulated Mold Open Dwell Time [21]
SYS59
Accumulated Mold O en Dwell Time [21]
If bit patterns in MCC02 and MCC03 indicate that the module is connected to a clamp position transducer, the module:
reports the accumulated value of its internal Mold Open Dwell timer (maximum 99 99 seconds) in this word
S
reports the accumulated value of its internal Mold Open Dwell timer (maximum 99.99 seconds) in this word.
S
sets master status bit SYS03-B09 when the timer is timing
S
sets master status bit SYS03-B09 when the timer is timing.
S
stops the timer, resets SYS03-B09, and resets this word to zero upon receipt of any action execution command bit
S
sto s the timer, resets SYS03-B09, and resets this word to zero u on recei t of any action execution command bit
except DYC02-B14 (execute ejector profile).
SYS60
Accumulated Cycle Time [22]
If bit patterns in MCC02 and MCC03 indicate that the module is connected to a clamp position transducer, the module:
S
resets this word to zero and starts an internal cycle timer when it detects an F-to-T transition of DYC02-B00
S
stops this timer when it sets master status bit SYS03-B11 and reports the accumulated value of the timer (maximum
of 999.9 seconds) in this word
Diagnostics
Word
Description
SYS61
Programming Error Block
Module reports in the lower byte of this word a bit pattern copy of the block id associated with the command block that contained the
error referred to in SYS62. The priority order to be used by the module when reporting programming error codes will be as follows:
S
any MCC programming error
S
any DYC programming error
S
any programming error associated with DYC61
S
any other current programming error
SYS62
Programming Error Code
SYS63
Module Series/Revision
Upper byte - The module reports its firmware series in ASCII.
Lower byte - The module reports its firmware revision in ASCII.
New Status Confirmation
Word
Description
SYS64
New data counter. The module sets this counter to zero on power start-up or above 9999, and increments this counter when it
sends a new SYS to its internal TIC chip.
Use this value to indicate that a most recent BTR of SYS is old data (last SYS64 equals new SYS64) or new data (last SYS64 is less
than new SYS64). You may also monitor the value to determine if you are missing any data (last SYS + 1 is less than new SYS64).