Rockwell Automation 1771-QDC PLASTIC MOLD.MODULE User Manual
Page 83
2–17
Command Word/Bit Descriptions
Publication 1771-6.5.88 – July 1997
DYC
Word
Bit
Description
DYC02
B05
if:
then the module:
= 0 Normal
= 1 Execute Pack Profile
A false-to-true transition of this bit forces the module to do
one of the following, attempted in the order listed.
if:
then the module:
any of SYS07-B00 through B05 are SET
ignores any profile commands
SYS15-B11 is RESET
latches SYS13-B06
HPC11 is not zero
terminates any action in progress and
starts the Pack Profile
HPC11 is zero
terminates any action in progress and
starts the Hold Profile
B06
= 0 Normal
= 1 Execute Hold Profile
A false-to-true transition of this bit forces the module to do
one of the following, attempted in the order listed.
if:
then the module:
any of SYS07-B00 through B05 are SET
ignores any profile commands
SYS15-B11 is RESET
latches SYS13-B07
this bit (B06) is SET
terminates any action in progress and
starts the Hold Profile
B07
= 0 Normal
= 1 Execute Pre-decompression Movement
A false-to-true transition of this bit forces the module to do
one of the following, attempted in the order listed.
if:
then the module:
any of SYS07-B00 through B05 are SET
ignores any movement commands
either of the following are true:
– SYS15-B11 is RESET
– HPC03-B09 is SET and SYS15-B12 is RESET
latches SYS13-B08
all of the following are true:
– PRC05 equals zero or SYS15-B12 is RESET
– HPC03-B09 is RESET
– SYS15-B14 is RESET
latches SYS13-B09
PRC05 is not zero
terminates any action in progress and
starts the Pre-decompression Movement
both of the following are true:
– PRC05 is zero
– HPC03-B09 is SET
terminates any action in progress and
sets outputs to PRC33 - PRC40
either pair of the following are true:
– PRC05 is zero
or
– SYS15-B12 is RESET
– HPC03-B09 is RESET
– HPC03-B09 is RESET
terminates any action in progress and
starts the Plastication Profile