Ue] and, Par 468 – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual
Page 85

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013
85
Programming and Parameters
Chapter 2
468
MC TP1 Bit
Displays the data selected by
[MC TP1 Select]. This display should only be used if the selected value is
bit-enumerated data. Par 468 [MC TP1 Bit] is a diagnostic tool you can use to view internal drive parameters.
Default:
Min:
Max:
00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111
RO
32-bit
Boolean
469 FVC
CEMF
Comp
Displays the current regulator feedforward compensation. Do not change this value.
Default:
Min/Max:
Units:
0
0/100
%
RW 16-bit
Integer
470
Flux Reg P Gain2
Displays the additional proportional gain used at the start of Bus voltage limited field weakening. Do not
change this value.
Default:
Min/Max:
1000
0/32767
RW 16-bit
Integer
471
Estimated Torque
Displays the calculated motor shaft torque.
Notes: This parameter was added for firmware version 2.003. The Units and Scale information were added for
firmware version 4.002.
Default:
Min/Max:
Units:
Scale:
0.0
+/-8.0 P.U.
P.U.
1.0 = 100% of the Motor Torque
RO
Real
472 PreCharge
Delay
Adjusts the delay between the time all other precharge conditions have been met and the time the drive
leaves the precharge state. Can be used to control the sequence of precharge completion in a drive system.
The maximum value of this parameter is calculated as follows:
Par 472 [PreCharge Delay] =
[PreChrg TimeOut] - 1.0 second.
Default:
Min/Max:
Units:
2.0
0.0/Calculated
s
RW 16-bit
Integer
No.