Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual
Page 79

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013
79
Programming and Parameters
Chapter 2
No.
Name
Description
Values
Li
nk
ab
le
Re
ad
-W
ri
te
Da
ta
T
ype
412
Power EE TP Sel
Enter or write a value to select drive power EEPROM data displayed in
[Power EE TP Data]. The default is 0 “Zero”.
Note: Options 74 - 92 were changed and options 93 - 111 were added for firmware version 3.001.
413
Power EE TP Data
Displays the data selected by
[Power EE TP Sel].
Default:
Min/Max:
0
-/+2200000000
RO
Real
414 Brake/Bus
Cnfg
Configures the brake and bus operation of the drive.
• Set bit 0 “Brake Enable” to enable the operation of the internal brake transistor.
• Set bit 1 “Brake Extern” to configure the brake to use an external resistor.
• Set bit 2 “Bus Ref High” to select the “high” voltage setting as the turn-on point for the Bus Voltage Regulator. With the “high” setting brake operation starts when bus voltage reaches the value
[BusReg/Brake Ref], and Bus Voltage Regulator operation starts when bus voltage reaches the value of Par 415 [BusReg/Brake Ref] plus 4.5%. With the “low” setting, the bus
regulator turns on first at the value set by Par 415 [BusReg/Brake Ref] and then the dynamic braking turns on when there are any transients above the value set in Par 415 [BusReg/Brake Ref].
• Set bit 3 “Bus Reg En” to enable the Bus Voltage Regulator. The output of the Bus Voltage Regulator is summed with
[Regen Power Lim] and fed into the Power Limit Calculator. It, in
effect, reduces regenerative torque references when the bus voltage is too high.
Notes: This parameter was changed to non-linkable and bits 5 and 6 were added for future use - not active for use with firmware version 3.001. Remove bits 5 and 6 for firmware version 4.001 - not
used.
415 BusReg/Brake
Ref
Sets the “turn-on” voltage for the bus regulator and brakes. Enter a percentage of the high voltage setting for
the voltage class. For example, on a 400…480V AC drive,
Note: The minimum value for frame 5 and up, 600V AC input drives was changed from 110.5000 to 100.0000
for firmware version 4.002.
(1) The minimum value is 100.0000 for frame 5 and up, 600V AC input drives.
Default:
Min/Max:
Units:
111.0000
110.5000
(1)
/117.8000
%
RW Real
416 Brake
PulseWatts
Limits the power delivered to the external Dynamic Brake (DB) resistor for one second, without exceeding the
rated element temperature. You may change the value of this parameter only if you have selected an external
DB resistor (set bit 1 “Brake Extern” of
[Brake/Bus Cnfg]. If this rating is not available from the resistor
vendor, you can approximate it with this equation:
[Brake PulseWatts] = 75,000 x Weight, where
Weight equals the weight of resistor wire element in pounds (not the entire weight of the resistor). Another
equation you can use is: Par 416 [Brake PulseWatts] = Time Constant x Brake Watts; where Time Constant
equals the amount of time to reach 63% of its rated temperature while the maximum power is applied, and
Brake Watts is the peak power rating of the resistor.
Note: The maximum value was changed from 1000000.0000 to 1000000000.0000 for firmware version 3.001.
Default:
Min/Max:
Units:
2000.0000
1.0000/1000000000.0000
W
RW Real
Options:
0 = Zero
19 = Bus VltScale
38 = IGBT Rated A
61 = Convt Type
80 = HH1 P/B ID
99 =
HH2 P/B ID
1 = Volt Class
20 = Sml PS Watts
39 = IGBT V Thres
62 = DC Bus Induc
81 = HH1 S/W ID
100 = HH2 S/W ID
2 = Assy Rev
21 = Sml PS Min V
40 = IGBT Slope R
63 = AC Inp Induc
82 = HH1 P/B Rev
101 = HH2 P/B Rev
3 = ASA S/N
22 = Lrg PS Watts
41 = IGBT Sw Engy
64 = Precharg Res
83 = HH1 S/W Rev
102 = HH2 S/W Rev
4 = Manuf Year
23 = Lrg PS Min V
44 = IGBT CS Tres
65 = PrechThrm Tc
84 = HH1 Extr Data
103 = HH2 ExtrData
5 = Manuf Month
24 = Inv Rated Kw
45 = IGBT CS Tc
66 = Mtr NP Units
85 = HH1 VoltIndx
104 = HH2 VoltIndx
6 = Manuf Day
25 = Inv Rated V
46 = Diode V Thrs
67 = Mtr NP Power
86 = HH1 SizeIndx
105 = HH2 SizeIndx
7 = Tst ProcStat
26 = Inv Rated A
47 = Diode SlopeR
68 = Mtr NP Volts
87 = HH1 Option
106 = HH2 Option
8 = Life PwrCycl
27 = Inv 1min Amp
48 = Diode JC Tr
69 = Mtr NP Amps
88 = HH1 HrdPrdct
107 = HH2 HrdPrdct
9 = Life Pwrup
28 = inv 3sec Amp
49 = Diode JC Tc
70 = Mtr NP Freq
89 = HH1 H/W Mdfy
108 = HH2 H/W Mdfy
10 = Life RunTime
29 = SW OverC Amp
50 = GBT Tjmax
71 = Mtr NP RPM
90 = HH1 1V/Amp
109 = HH2 1V/Amp
11 = Kw Accum
30 = DC Bus Cap
51 = HS Max DegC
72 = Mtr IR Vdrop
91 = HH1 2s/Amp
110 = HH2 2s/Amp
12 = Mw Hrs Accum
31 = Min PWM Khz
52 = DB IGBT Amp
73 = Mtr Id Ref
92 = HH1 Scale
111 = HH2 Scale
13 = Inv High Vlt
32 = Max PWM Khz
53 = DB ohms
74 = HH1 Data Rev
93 = HH2 Data Rev
14 = Reserved
33 = Dfl PWM Khz
54 = DB E Jo/degC
75 = HH1 Dev Type
94 = HH2 Dev Type
15 = Fan/Pwr Cntl
34 = PWM Dead us
55 = DB EB C/Watt
76 = HH1 Serial #
95 = HH2 Serial #
16 = Temp Sensor
35 = Drive Frame
56 = DB B Jo/degC
77 = HH1 Test Date
96 = HH2 TestDate
17 = Phs AmpScale
36 = IGBTs per Pk
57 = DB BA C/Watt
78 = HH1 Vcn Code
97 = HH2 Vcn Code
18 = Gnd AmpScale
37 = GBT Rated V
60 = DB Ambt Tmax
79 = HH1 CrsCncID
98 = HH2 CrsCncID
Options
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Bu
s Re
g En
Bu
s Re
f H
ig
h
Brak
e Ex
ter
n
Brak
e E
na
ble
Default
x
x
x
x
x
x
x
x
x
x
x
x
1
1
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True
111
2
×
480 VDC
=