Chapter 3
Troubleshooting
Drive Status Indicators
Table 3 - Drive Status Indicator Descriptions
1
2
3
#
Name
Color
State
Description
DR
IV
E
Po
w
er S
truc
ture
1
PWR (Power)
Green
Steady
Illuminates when power is applied to the drive.
2
STS
(Status)
Green
Flashing
Drive ready, but not running & no faults are present.
Steady
Drive running, no faults are present.
Yellow
Flashing
When running, a type 2 (non-configurable) alarm condition exists, drive continues to run. When
stopped, a start inhibit exists and the drive cannot be started.
Steady
A type 1 (user configurable) alarm condition exists, but drive continues to run.
Red
Flashing
A fault has occurred.
Steady
A non-resettable fault has occurred.
Red /
Yellow
Flashing
Alternately
The drive is in flash recovery mode. The only operation permitted is flash upgrade.
Co
nt
ro
l A
sse
mbly
Co
mmunic
at
io
ns 3
PORT
Refer to the
Communication Adapter
User Manual
Status of DPI port internal communications (if present).
MOD
Status of communications module (when installed).
NET A
Status of network (if connected).
NET B
Status of secondary network (if connected).
Co
nt
ro
l
(1)
SYNCHLINK
Green
Steady
The module is configured as the time keeper.
or
The module is configured as a follower and synchronization is complete.
Green
Flashing
The follower(s) are not synchronized with the time keeper.
Red
Flashing
The module is configured as a time master on SynchLink and has received time information from
another time master on SynchLink.
ENABLE
Green
On
The drive’s enable input is high.
Green
Off
The drive’s enable input is low.