Par 852 – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual
Page 116
![background image](/manuals/576845/116/background.png)
116
Rockwell Automation Publication 20D-PM001C-EN-P - July 2013
Chapter 2
Programming and Parameters
852
Dig Out 2 Bit
Selects the bit, from the word linked to
[Dig Out 2 Data], that will change the status of Digital Output 2
[Dig Out 2 Bit] equals 0, bit 0 of Par 851 [Dig Out 2 Data] will control Digital Output 2).
Default:
Min/Max:
0
-32/31
Y
RW 16-bit
Integer
853
Dig Out2 On Time
Defines the amount of time between a False to True transition on the output status and the corresponding
change in state of Digital Output 2. If a transition on an output condition occurs and starts the time delay and the
output condition returns to its original state before the delay timer reaches the setpoint, the delay timer will be
aborted and the corresponding output status or digital output will not change state. Par 853 [Dig Out2 On Time]
can be disabled by setting the delay time to 0 (zero).
Note: This parameter was added for firmware version 3.001.
Default:
Min/Max:
Units:
0.00
0.00/600.00
s
RW 16-bit
Integer
854
Dig Out2 OffTime
Defines the amount of time between a True to False transition on the output status and the corresponding
change in state of Digital Output 2. If a transition on an output condition occurs and starts the time delay and the
output condition returns to its original state before the delay timer reaches the setpoint, the delay timer will be
aborted and the corresponding output status or digital output will not change state.
Note: This parameter was added for firmware version 3.001.
Default:
Min/Max:
Units:
0.0
0.0/600.00
s
RW 16-bit
Integer
855
Rly Out3 Sel
Identifies the signal used on Digital Output 3. If the desired signal is not available in the selection list, choose
option 0 - “User Select” and link with
[Rly Out3 Data] and
[Rly Out3 Bit] to select the desired
parameter for output.
Default:
Options:
1 =
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =
“Not Fault”
“User Select”
15 = “Torque Limit”
“Not Fault”
16 = “Power Limit”
“Not Alarm”
17 = “Fault”
“Ready”
18 = “Alarm”
“Running”
19 = “Command Dir”
“Reserved”
20 = “Actual Dir”
“Reserved”
21 = “Jogging”
“Enable On”
22 = “In Position”
“Active”
23 = “Posit Watch1”
“At Speed”
24 = “Posit Watch2”
“At Setpt 1”
25 = “Cmpr 1 A=B”
“Above Setpt 2”
26 = “Cmpr 1 A>/=B”
“At ZeroSpeed”
27 = “Cmpr 2 A=B”
“Speed Limit”
28 = “Cmpr 2 A>/=B”
“CurrentLimit”
856
Rly Out3 Data
Link a word to this parameter that will control the Relay Output 3. The bit within the selected word that will
control Relay Output 3 is set by
[Rly Out3 Bit].
Default:
Min:
Max:
00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111
Y
RW 32-bit
Boolean
857
Rly Out3 Bit
Selects the bit, from the word linked to
[Rly Out3 Data] that will change the status of the Relay Output 3
(e.g., when Par 857 [Rly Out3 Bit] equals 0, bit 0 of Par 856 [Rly Out3 Data] will control the Relay Output 3).
Default:
Min/Max:
0
-32/31
Y
RW 16-bit
Integer
858
Rly Out3 On Time
Defines the amount of time between a False to True transition on the output status and the corresponding
change in state of Relay Output 3. If a transition on an output condition occurs and starts the time delay and the
output condition returns to its original state before the delay timer reaches the setpoint, the delay timer will be
aborted and the corresponding output status or relay output will not change state. Par 858 [Rly Out3 On Time]
can be disabled by setting the delay time to 0 (zero).
Note: This parameter was added for firmware version 3.001.
Default:
Min/Max:
Units:
0.00
0.00/600.00
s
RW 16-bit
Integer
859
Rly Out3 OffTime
Defines the amount of time between a True to False transition on the output status and the corresponding
change in state of Relay Output 3. If a transition on an output condition occurs and starts the time delay and the
output condition returns to its original state before the delay timer reaches the setpoint, the delay timer will be
aborted and the corresponding output status or relay output will not change state.
Note: This parameter was added for firmware version 3.001.
Default:
Min/Max:
Units:
0.00
0.00/600.00
s
RW 16-bit
Integer
General BitSwap Description
The six (6) Bit Swap functions are used to replace one bit in a word with one bit from a different word. This is typically done to a control word where one bit in the control word
is replaced by a bit from another word such as a digital input. Four (4) input parameters and one (1) output parameter are used to accomplish each Bit Swap function. Refer to
the User Functions 1 block diagram on
860
865
870
875
880
885
BitSwap 1A Data
BitSwap 2A Data
BitSwap 3A Data
BitSwap 4A Data
BitSwap 5A Data
BitSwap 6A Data
This is the main word in which 1 bit will be edited. All of the data from this word except the selected bit in
[BitSwap 1A Bit] are passed to
[BitSwap 1 Result].
Default:
Min/Max:
0
32 bits of data
Y
RW 32-bit
Boolean
861
866
871
876
881
886
BitSwap 1A Bit
BitSwap 2A Bit
BitSwap 3A Bit
BitSwap 4A Bit
BitSwap 5A Bit
BitSwap 6A Bit
This parameter specifies the bit to be replaced in
[BitSwap 1A Data].
Default:
Min/Max:
0
0/31
RW 16-bit
Integer
No.
Name
Description
Values
Link
able
Re
ad
-Write
Da
ta
T
yp
e