Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual
Page 69

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013
69
Programming and Parameters
Chapter 2
334
700L AlarmStatus
Indicates the occurrence of exception events that have been configured as alarm conditions for PowerFlex 700L (LiquiFlo) drive.
• Bit 0 “NonCnfgFault” Not configured as alarm.
• Bit 1 “NonCnfgFault” Not configured as alarm.
• Bit 2 “NonCnfgFault” Not configured as alarm.
• Bit 3 “NonCnfgFault” Not configured as alarm.
• Bit 4 “NonCnfgFault” Not configured as alarm.
• Bit 5 “NonCnfgFault” Not configured as alarm.
• Bit 6 “NonCnfgFault” Not configured as alarm.
• Bit 7 “NonCnfgFault” Not configured as alarm.
• Bit 8 “NonCnfgFault” Not configured as alarm.
• Bit 14 “NonCnfgFault” Not configured as alarm.
• Bit 15 “NonCnfgFault” Not configured as alarm.
• Bit 16 “NonCnfgFault” Not configured as alarm.
• Bit 17 “NonCnfgFault” Not configured as alarm.
• Bit 18 “NonCnfgFault” Not configured as alarm.
• Bit 19 “NonCnfgFault” Not configured as alarm.
• Bit 20 “NonCnfgFault” Not configured as alarm.
• Bit 21 “NonCnfgFault” Not configured as alarm.
• Bit 22 “NonCnfgFault” Not configured as alarm.
• Bit 23 “NonCnfgFault” Not configured as alarm.
• Bit 24 “NonCnfgFault” Not configured as alarm.
Note: This parameter was added for firmware version 2.003.
335
Abs OverSpd Lim
Sets an incremental speed above
Par 76
[Fwd Speed Limit] and below
[Rev Speed Limit] that is allowable
before the drive indicates its speed is out of range.
Default:
Min/Max:
Units:
Scale:
352.8000
0.0000/1750.0000
rpm
[Motor NP RPM] = 1.0 P.U.
RW Real
336 Motor
OL
Factor
Sets the minimum level of current that causes a motor overload trip under continuous operation. Current levels
below this value will not result in an overload trip. For example, a service factor of 1.15 implies continuous
operation up to 115% of nameplate motor current.
Default:
Min/Max:
Units:
1.1500
1.0000/2.0000
P.U.
RW Real
337
Mtr I2T Curr Min
Sets the minimum current threshold for the motor overload (I
2
T) function. The value indicates minimum current
at the minimum speed,
[Mtr I2T Spd Min], and these are the first current/speed breakpoint. From this
point the current threshold is linear to the value specified by
[Motor OL Factor].
Default:
Min Max:
Units:
0.5000
0.0500/2.0000
P.U.
RW Real
338
Mtr I2T Spd Min
Sets the minimum speed for the motor overload (I
2
T) function. The value indicates minimum speed below the
minimum current threshold
[Mtr I2T Curr Min], and these are the first current/speed breakpoint. From this
point the current threshold is linear to the value specified by the motor service factor
[Motor OL Factor].
Set this parameter to the minimum value for the motor overload trip to vary in time at low speeds. For more
information, please see Motor Overload on page
.
Default:
Min/Max:
Units:
1.0000
0.0500/1.0000
P.U.
RW Real
339
Mtr I2T Calibrat
Sets the current calibration level for the motor overload (I
2
T) function. The value indicates the current level that
the drive will fault at this current in 60 seconds.
Default:
Min/Max:
Units:
2.0000
1.1000/4.0000
P.U.
RW Real
340
Mtr I2T Trp ThrH
Displays the trip threshold current for the motor overload (I
2
T) function. The value depends on the motor speed,
and is calculated from the minimum current
[Mtr I2T Curr Min], the minimum speed
[Mtr I2T Spd
Min] and the motor service factor
[Motor OL Factor].
Default:
Min/Max:
Units:
1.1500
0.0500/2.0000
P.U.
RO
Real
341
Mtr I2T Count
The accumulator for Motor Overload detection (Motor I
2
T function). When the motor runs at the over rated motor
current, the accumulator starts counting up. If the motor runs at below rated motor current, the accumulator
counts down. If the value of this parameter exceeds 0.5, the “Motor OLoad Pend” alarm (fault 12) occurs. If the
value of this parameter exceeds 1.0, the “Motor OLoad Trip” fault (fault 11) occurs. The value of this parameter is
saved in non-volatile memory after power-down if
[Control Options], bit 20 “Motor OL Ret” is on. Toggling
bit 20 of Par 153 [Control Options] clears the value of this parameter.
Note: This parameter was added for firmware version 3.001.
Default:
Min/Max:
0.0
0.0/1.5
RO
Real
No.
Name
Description
Values
Link
able
Re
ad
-Write
Da
ta
T
yp
e
Options
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
N
onC
nfgF
ault
Default
x
x
x
x
x
x
x
0
0
0
0
0
0
0
0
0
0
0
x
x
x
x
x
0
0
0
0
0
0
0
0
0
Bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True