Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual
Page 73
Rockwell Automation Publication 20D-PM001C-EN-P - July 2013
73
Programming and Parameters
Chapter 2
375
Inv OT Pend Cnfg
Enter a value to configure the drive's response to a Inverter Over-Temperature (OT) Pending exception event. This
event is triggered when the Inverter Negative Temperature Coefficient (NTC) function detects the heat-sink
temperature reaches to the overload warning level.
• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
• 3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to
this event.
• 4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in
response to this event.
Default
Options:
1 =
0 =
1 =
2 =
3 =
4 =
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
376
Inv OL Pend Cnfg
Enter a value to configure the drive's response to an Inverter Overload (OL) Pending exception event. This event is
triggered when one of the Inverter Protection Current-Over-Time functions (Open Loop or Closed Loop) detects
current and temperature at warning levels.
• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
• 3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to
this event.
• 4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in
response to this event.
Default
Options:
1 =
0 =
1 =
2 =
3 =
4 =
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
377
Inv OL Trip Cnfg
Enter a value to configure the drive's response to an Inverter Overload (OL) Trip exception event. This event is
triggered when one of the Inverter Protection Current-Over-Time functions (Open Loop or Closed Loop) detects
current and temperature at a fault level.
• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
Default:
Options:
1 =
0 =
1 =
2 =
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
378
Interp Flt Cnfg
Enter a value to configure the drive's response to a position interpolator exception event. If the interpolator loses
the synchronization pulse or is out of synch, this event occurs.
Default:
Options:
1 =
0 =
1 =
2 =
“Alarm”
“Ignore”
3 = “Flt RampStop”
“Alarm”
4 = “FltCurLimStp”
“FltCoastStop”
379
Ext Flt/Alm Cnfg
Enter a value to configure the drive's response to an External Input exception event. The event is triggered by a
digital input that is configured for auxiliary fault or auxiliary aux fault by selecting 3 “Ext Fault” or 38 “ExtFault
Inv” in
[DigIn 1 Sel],
[DigIn 2 Sel] or
[DigIn 3 Sel].
• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
• 3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to
this event.
• 4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in
response to this event.
Default
Options:
2 =
0 =
1 =
2 =
3 =
4 =
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
381
PreChrg Err Cnfg
Enter a value to configure the drive's response to a Precharge Error exception event.
• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event
Default:
Options:
2 =
0 =
1 =
2 =
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
382
MC Cmd Lim Cnfg
Enter a value to configure the drive's response to a Motor-Controller (MC) Command Limitation exception event.
This event is triggered when the motor-controller detects limit of the command values used in the motor-
controller, and returns the exception event to the Velocity Position Loop (VPL).
• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
Default:
Options:
2 =
0 =
1 =
2 =
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
No.
Name
Description
Values
Link
able
Re
ad
-Write
Da
ta
T
yp
e