beautypg.com

Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 73

background image

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

73

Programming and Parameters

Chapter 2

375

Inv OT Pend Cnfg

Enter a value to configure the drive's response to a Inverter Over-Temperature (OT) Pending exception event. This
event is triggered when the Inverter Negative Temperature Coefficient (NTC) function detects the heat-sink
temperature reaches to the overload warning level.
• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to

this event.

• 3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to

this event.

• 4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in

response to this event.

Default

Options:

1 =

0 =
1 =
2 =
3 =
4 =

“Alarm”

“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

376

Inv OL Pend Cnfg

Enter a value to configure the drive's response to an Inverter Overload (OL) Pending exception event. This event is
triggered when one of the Inverter Protection Current-Over-Time functions (Open Loop or Closed Loop) detects
current and temperature at warning levels.
• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to

this event.

• 3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to

this event.

• 4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in

response to this event.

Default

Options:

1 =

0 =
1 =
2 =
3 =
4 =

“Alarm”

“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

377

Inv OL Trip Cnfg

Enter a value to configure the drive's response to an Inverter Overload (OL) Trip exception event. This event is
triggered when one of the Inverter Protection Current-Over-Time functions (Open Loop or Closed Loop) detects
current and temperature at a fault level.
• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to

this event.

Default:

Options:

1 =

0 =
1 =
2 =

“Alarm”

“Ignore”
“Alarm”
“FltCoastStop”

378

Interp Flt Cnfg

Enter a value to configure the drive's response to a position interpolator exception event. If the interpolator loses
the synchronization pulse or is out of synch, this event occurs.

Default:

Options:

1 =

0 =
1 =
2 =

“Alarm”

“Ignore”

3 = “Flt RampStop”

“Alarm”

4 = “FltCurLimStp”

“FltCoastStop”

379

Ext Flt/Alm Cnfg

Enter a value to configure the drive's response to an External Input exception event. The event is triggered by a
digital input that is configured for auxiliary fault or auxiliary aux fault by selecting 3 “Ext Fault” or 38 “ExtFault
Inv” in

Par 825

[DigIn 1 Sel],

Par 826

[DigIn 2 Sel] or

Par 827

[DigIn 3 Sel].

• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to

this event.

• 3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to

this event.

• 4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in

response to this event.

Default

Options:

2 =

0 =
1 =
2 =
3 =
4 =

“FltCoastStop”

“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

381

PreChrg Err Cnfg

Enter a value to configure the drive's response to a Precharge Error exception event.
• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to

this event

Default:

Options:

2 =

0 =
1 =
2 =

“Alarm”

“Ignore”
“Alarm”
“FltCoastStop”

382

MC Cmd Lim Cnfg

Enter a value to configure the drive's response to a Motor-Controller (MC) Command Limitation exception event.
This event is triggered when the motor-controller detects limit of the command values used in the motor-
controller, and returns the exception event to the Velocity Position Loop (VPL).
• 0 - Ignore configures the drive to continue running, as normal, when this event occurs.
• 1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
• 2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to

this event.

Default:

Options:

2 =

0 =
1 =
2 =

“Alarm”

“Ignore”
“Alarm”
“FltCoastStop”

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e