Par 27, Speed ref, Par 28 – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual
Page 34: With, Speed r, E to, Par 38
![background image](/manuals/576845/34/background.png)
34
Rockwell Automation Publication 20D-PM001C-EN-P - July 2013
Chapter 2
Programming and Parameters
No.
Name
Description
Values
Li
nk
ab
le
Re
ad
-W
ri
te
Da
ta
T
ype
26
SpdTrim2 Filt BW
Sets the frequency for the Speed Trim 2 filter.
Default:
Min/Max:
Units:
200.0000
0.0000/1000.0000
rad/s
Y
RW Real
27
28
Speed Ref A Sel
Speed Ref B Sel
Selects the speed reference source for the drive. The selected speed reference values converge in the final
selection of the drives speed reference with
[Applied LogicCmd] and are selected with bits 28, 29, 30.
See the Block Diagrams beginning on page
for a description.
Default A:
Default B:
Options:
1 =
5 =
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
“Spd Ref 1”
“Preset Spd 1”
“Zero Speed”
9 = “Preset Spd 5”
“Speed Ref 1”
10 = “Preset Spd 6”
“Speed Ref 2”
11 = “Preset Spd 7”
“Sum Sref 1+2”
12 = “DPI Port 1”
“MOP Level”
13 = “DPI Port 2”
“Preset Spd 1”
14 = “DPI Port 3”
“Preset Spd 2”
15 = “Reserved”
“Preset Spd 3
16 = “DPI Port 5”
“Preset Spd 4”
29
Jog Speed 1
Sets the speed reference that the drive should use when responding to bit 18 [Jog 1] of
[Applied LogicCmd].
Default:
Min/Max:
Units:
Scale:
0.0000
-/+8.0000 P.U.
rpm
[Motor NP RPM] = 1.0 P.U.
Y
RW Real
30
Min Spd Ref Lim
Sets the minimum speed reference limit. This value may be negative or positive but not greater than
[Max Spd Ref Lim].
Default:
Min/Max:
Units:
Scale:
0.0000
-8.0000/Par 31 [Max Spd Ref Lim]
rpm
[Motor NP RPM] = 1.0 P.U.
RW Real
31
Max Spd Ref Lim
Sets the maximum speed reference limit. This value may be negative or positive but not less than
[Min Spd Ref Lim].
Default:
Min/Max:
Units:
Scale:
0.0000
Par 30 [Min Spd Ref Lim]/8.0000
rpm
[Motor NP RPM] = 1.0 P.U.
RW Real
32
Accel Time 1
Sets the rate of acceleration for all speed increases, with time in seconds to base speed.
Accel Rate =
[Motor NP RPM] /
[Accel Time]
Default:
Min/Max:
Units:
10.0000
0.0100/6553.5000
s
Y
RW Real
33
Decel Time 1
Sets the rate of deceleration for all speed decreases, with time in seconds to base speed.
Decel Rate =
[Decel Time]
Default:
Min/Max:
Units:
10.0000
0.0100/6553.5000
s
Y
RW Real
34
S Curve Time
Sets the S time (Round In and Round Out ) in seconds. Half of the time specified is added to the beginning and
half to the end of the applied ramp. The S time is independent of speed and results in a trapezoidal torque profile.
For example:
Default:
Min/Max:
Units:
0.5000
0.0000/4.0000
s
Y
RW Real
35
SpdRef Filt Gain
Sets the lead term for the Speed Reference filter. Values greater than 1 will result in a lead function and values
less than 1 will result in a lag function. A value of 1 will disable the filter.
Default:
Min/Max:
1.0000
-/+5.0000
Y
RW Real
36
SpdRef Filt BW
Sets the frequency for the Speed Reference filter.
Default:
Min/Max:
Units:
0.0000
0.0000/500.0000
rad/s
Y
RW Real
37
Spd Ref Bypass
The speed command after the limit, ramp and s-curve blocks. Link a source directly to this parameter to bypass
these blocks.
Default:
Min/Max:
Units:
Scale:
0.0000
-/+14112.0000
rpm
[Motor NP RPM] = 1.0 P.U.
Y
RW Real
38
Speed Ref Scale
This parameter is multiplied with the value in
[Spd Ref Bypass].
Default:
Min/Max:
1.0000
-/+1000.0000
Y
RW Real
39
Jog Speed 2
Sets the speed reference that the drive should use when responding to bit 23 [Jog 2] of
[Applied LogicCmd].
Default:
Min/Max:
Units:
Scale:
0.0000
-/+8.0000 P.U.
rpm
[Motor NP RPM] = 1.0 P.U.
Y
RW Real
S Curve Time = 1.0 second
Speed
Time in Seconds
0.5 sec.
Accel Time = 5.0 seconds
Total Ramp Time = 6.0 seconds
0.5 sec.