Model 493.74 two-station hsm interface board, Model 493.74 two-station hsm interface board 246 – MTS FlexTest Models 200 User Manual
Page 246

MTS FlexTest® Models 40/60/100/200 Controller Hardware
Model 493.74 Two-Station HSM Interface Board
Digital I/O and Transition Boards
246
Model 493.74 Two-Station HSM Interface Board
About the Model 493.74 Two-Station HSM Interface Board
The Model 493.74 Two-Station HSM Interface
board is a double-width board that plugs into the
transition card cage on a Series 494 Chassis.
Each Model 493.74 HSM transition board
controls up to two stations.
Each station has the following connections:
•
24-volt hydraulic service manifold (HSM)
control (off/low/high or proportional) (J28
HSM)
•
E-Stop and crosshead controls for a load
unit control module (J29 Load Frame)
•
Inputs that can initiate station and program
interlocks (J43 Interlock)
•
Remote run/stop outputs for external
devices (J44 Run/Stop)
•
Auxiliary power outputs for external
devices (J49 Aux Power)
Intlk
J28B HSM
R
J43-1
J43-2
Run/Stop
J44-1
J44-2
Aux Power
J49-1
J49-2
Load Frame
J29-1
J29-2
J28A HSM
493.74
HSM
Station
J49 Aux Power
Fused auxiliary DC supply
voltages for external devices.
+ 5 V DC, +15 V DC,
-15 V DC, and +24 V DC
J28A/B HSM
24-volt control for HSM off/
low/high or proportional
solenoids.
J43-1/2 Intlk
Station and Program
Interlock inputs
J44-1/2 Run/Stop
Run/Stop output contacts
Interlock out (opto isolators)
J29-1/2 Load Frame
E-Stop and crosshead
controls for each station