Deleting sdsl frame alarm profiles – ADC AVIDIA SWD4573I1 User Manual
Page 422

Configuring SDSL Frame Alarm Profiles
396
Avidia System Configuration and Management User Manual
4
In the
Alarm Setting UAS
box, select the desired unavailable seconds alarm setting (
disable
,
enable
).
5
In the
Threshold Margin
box, type the desired margin threshold, in decibels.
When the margin falls below the specified threshold, the margin alarm is activated. A
typical margin threshold value is 6.
6
In the
Threshold ES
box, type the desired errored seconds threshold.
When the number of errored seconds in the current 15-minute data collection interval
exceeds the specified threshold, the errored seconds alarm is activated. Errored seconds are
seconds during which errors occur that prevent the payload from being corrected. A typical
errored second threshold value is 17.
7
In the
Threshold UAS
box, type the desired unavailable seconds threshold.
When the number of unavailable seconds in the current 15-minute data collection interval
exceeds the specified threshold, the UAS alarm is activated. Unavailable seconds are
seconds during which the SDSL loop is not synchronized. A typical unavailable seconds
threshold value is 60.
8
Click
Add
to add the SDSL alarm profile.
Deleting SDSL Frame Alarm Profiles
1
In the
SDSL Alarm Profile Table
window, locate the table row that contains the SDSL alarm
profile you want to delete.
Click
and
if necessary to view the entire table.
displays the beginning of the
table.
displays the next page of the table.
2
Select the
Delete
check box next to the row that contains the profile you want to delete. To
select the
Delete
check box for all rows (except the default profile, which cannot be
deleted), click
Check All
.
If you decide not to delete a selected row, clear the
Delete
check box next to the row. Click
Clear All
to clear the
Delete
check box for all rows.
You cannot delete profiles that are assigned to ports.