Chapter 4: Resources

Doc.# 28002-00 Rev 3.00

Watlow Anafaze

35

To configure communications with the PPC-2000:

1.

Select the correct

Communication Port

for your PC.

2.

Select a

Parity

of

Even, Odd

or

None

.

3.

In the

Device Address

field, enter the controller

address for the PPC-2000.

4.

In the

ROM Size

field, enter 128kB. (Controllers with

2.03 and earlier firmware support up to 40 kB.

5.

Select a

Baud Rate

. The PPC-2000 supports

9600

and

19200

.

6.

In the

Time out

field, enter 2000 milliseconds.

7.

Click

[OK]

-or-
Click

[Cancel]

to exit this screen.

CPC400 Attributes

The CPC400 has the following default communication
settings:

Baud Rate: 19200

Controller Address: 1

To configure communications with the CPC400:

1.

Select the correct

Communication Port

for your PC.

2.

Select a

Parity

of

None

.

3.

In the

Device Address

field enter the controller

address you set in the CPC400.

4.

In the

ROM Size

field, enter 64 kB.

5.

Select a

Baud Rate

. The CPC400 supports

2400

,

9600

and

19200

.

6.

In the

Time out

field enter 2000 milliseconds.

7.

Click

[OK]

-or-
Click

[Cancel]

to exit this screen.