LogicPro User’s Guide

Chapter 12: Function Blocks

Doc.# 28002-00 Rev 3.00

Watlow Anafaze

195

PPC-2030 Encoder In Analog Out Addressing Example

To create a variable named CountIn_3 that reads the count on the
third input on a PPC-2030 module with its rotary address switch set
to 14, set the options in the Add Program/Resource Variable
dialog box as illustrated below.

Digital_IO_2040

The Digital_IO_2040 driver supports the inputs and outputs on the
PPC-2040 Digital IO Module.

To associate a variable with a digital I/O point:

1.

Open the Add Program/Resource Variable dialog box.

2.

Enter a unique variable Name.

3.

Select BOOL from the Type list.

4.

Select Input or Output by clicking the corresponding check
box.

5.

Select Digital_IO_2040 from the IO Driver list.

6.

Enter the IO Physical Address. The address is:
X.0.Z

X is the module address (21-26)
Z is the module I/O number (1-32).

7.

Click

[OK]

.