Chapter 12: Function Blocks

LogicPro User’s Guide

198

Watlow Anafaze

Doc.# 28002-00 Rev 3.00

Digital_Out_206x

The Digital_Out_206x driver supports the relay outputs on the PPC-
206x Digital Out series modules.

To associate a variable with a relay output:

1.

Open the

Add Program/Resource Variable

dialog box.

2.

Enter a unique variable

Name

.

3.

Select

BOOL

from the

Type

list.

4.

Select

Output

by clicking the check box.

5.

Select

Digital_Out_206x

from the

IO Driver

list.

6.

Select

BIT

from the

IO Size

list.

7.

Enter the

IO Physical Address

. The address is:

X.Z

X is the module address (41-46)
Z is the module I/O number (1-16)

8.

Click

[OK]

.

PPC-206x Digital Out Addressing Example

To create a variable named Relay_6 that sets the state of the 6

th

output on a PPC-206x module with its rotary address switch set to
41, set the options in the Add Program/Resource Variable
dialog box as illustrated below.