Section 4: Commissioning

10/08 97

51207 Revision 1

4.8.5 Configuring Limit Values


Each limit value consists of a switch-on and a switch-off point for definition of a hysteresis. The
three pairs of values must be entered according to the same principle. The limit values always refer
to the gross weight. Values between -0.01 x Max and 1.01 x Max of the relevant scale are
permissible.

Setup

Serial ports parameter

Date & Time

Operating parameter

Printing parameter

Fieldbus parameter

Network parameter

Calibration

Limit parameter

Press

and

Digital I/O parameter

to select [Limit parameter]

Setup/Limit parameter

Determine the limit values

Limit 1 on

890 kg

Action

-no action-

Limit 1 off

900 kg

Action

-no action-

Limit 2 on

300 kg

Action

-no action-

Limit 2 off

290 kg

Action

-no action-

Setup/Digital I/O parameter

Assign the outputs

Output 1

limit 1 out

X16=

1

Output 2

limit 2 out

X17=

1


Example: