beautypg.com

Fairbanks X SERIES PR 5410 Process Indicator User Manual

Page 38

background image

Section 3: Installing the Instrument and Plug-In Cards

10/08 38

51207 Revision 1

Outputs
PR 5510/09 outputs (pins 2 ... 24) use common GND as a reference potential and open collectors.
A non-activated output has high impedance, and an active output has a voltage by approximately
0.9 V higher than GND.
The load to be connected is applied between the collector [pins 2 … 24,(25*)] and Uext [PIN 1].

Input
When using as DATA_IN, the input (pin 25) can control the 23 outputs. As an output, data is
“continuous/hold/tristate“ and its signal can be configured (TTL/24V active (high/low). It is applied to
pin 25 – DATA_IN of the 26-pin connector and is effective only with DIL switch S101-1 = OFF and
S101-2 = ON.

Meaning of Switches S101 and S102

Fact. sett.

S101

-1

-2

-3

-4

-5

for:

OU

IN

Leve

l

Leve

l

Diod

e

As INPUT

DATA_IN

5V

Active

HIGH

Pin 25

OFF

ON

ON

ON

x

As INPUT

DATA_IN

5V

Active LOW

Pin 25

OFF

ON

ON

OFF

x

As INPUT

DATA_IN

24V

Active

HIGH

Pin 25

OFF

ON

OFF

ON

x

As INPUT

DATA_IN

24V

Active LOW

Pin 25

OFF

ON

OFF OFF

x

Free-wheel
diode*

internal

ON

Free-wheel
diode*

internal

OFF


Fact. sett.

S102

-1

-2

-3

-4

-5

for:

Func

tion

Func

tion

Func

tion

-

-

Pin25 INPUT

DATA_IN

follow

hold

Pin
2…24

OFF OFF

ON

x

x

DATA_IN

tristate

follow

Pin
2…24

ON

ON

OFF

x

x

DATA_IN

tristate

hold

Pin
2…24

ON

ON

ON

x

x


Signal level:

DATA IN

Logic level

I input

high

5 V mode

> 3.1 V

0.5 mA

low

5 V mode

< 1.5 V

0.3 mA

high

24 V mode

> 16 V

1.0 mA

low

24 V mode

< 10 V

0.5 mA