beautypg.com

Fairbanks X SERIES PR 5410 Process Indicator User Manual

Page 48

background image

Section 3: Installing the Instrument and Plug-In Cards

10/08 48

51207 Revision 1

3.4.11 PR 1721/34 DeviceNet Interface

DeviceNet interface PR 1721/34 is a plug-in card for installation in Slot 4; see Chapter 3.4.1. It is a
complete DeviceNet adaptor (slave) with CAN controller and transfer rates of up to 500 kbit/s.

Internal connection: 34-pin connector on flat cable, only

for Slot 4

External connection: 5-pin screw terminal block (plug-

in) in retainer plate

Transfer rates:

125, 250 and 500kbit/s

Topology:

Parallel bus

Protocol:

DeviceNet master-slave
Polling method (polled IO)
CRC error detection

to IEC 62026 (EN50325)

Max. 64 station nodes
Max. data width 512 bytes
input&output

Transport:

EIA RS-485

Configuration:

EDS file (PR 1721/34-specific)
MAC-ID (1…62)

Certificates/
conformity:

Compatible with DeviceNet
specification
Vol. 1: 2.0, vol. 2: 2.0
ODVA certificate in accordance with
conformity test software version A-12
Suitable for industrial applications CE,
UL & cUL

Cable:

DeviceNet, color: petrol-green
2x2 shielded twisted pair

Cable impedance: 150 ohms

Bus termination:

120 ohms at the cable ends

Dimensions
(LxWxH):

87 x 55 x 15 mm

Bus load:

33mA

Weight:

125 g

Electrical isolation: Yes, optocoupler and DC/DC

converter

Make sure DIP switches 1- 8 are set to ON.

Connecting diagram for a master with three slaves