Section 3: Installing the Instrument and Plug-In Cards
10/08 51
51207 Revision 1
3.4.13 PR 5510/14 ModBus TCP Interface
The Ethernet interface PR 5510/14 is a plug-in card for installation in Slot 4, Chapter 3.4.1. The card
is fitted with a standard RJ-45 socket for Ethernet connection.
It contains powerful TCP/IP and ModBus TCP connecting circuitry with transfer rates of 10 and
100Mbits/s.
Internal connection:
34-pin connector on flat cable
for Slot-4
External
connection:
RJ-45 connecting socket in holding
plate
Transfer rate:
10Mbits/sec (10BaseT , Ethernet) and
100Mbits/sec (100BaseTx, Fast
Ethernet)
Auto-detection (10/100, HalfDX/FullDX)
Connection mode:
Network
Protocol:
ModBus-TCP
Transport:
TCP/IP or UDP/IP
Certificates:
Compatible with ModBus-TCP standard
of ModBus organization
suitable for industrial applications CE,
UL, cUL
Cable:
Twisted pairs, screened
e.g. patch cable CAT5
Autolink (straight or crossover)
Cable impedance:
150 Ohm
Cable length to
HUB:
Max. 115 m
Dimensions
(LxWxH):
87 x 55 x 15mm Potential isolation:
Yes
Weight:
125 g
Application: ModBus TCP as a Fieldbus interface
The IP-Address and the Subnet-Mask are set at Fieldbus parameter FP 96 und 97. (see chapter
4.7.7 and Error! Reference source not found.).
Take care, that switches 1 - 8 are set to (OFF)