Section 3: Installing the Instrument and Plug-In Cards

10/08 51

51207 Revision 1

3.4.13 PR 5510/14 ModBus TCP Interface


The Ethernet interface PR 5510/14 is a plug-in card for installation in Slot 4, Chapter 3.4.1. The card
is fitted with a standard RJ-45 socket for Ethernet connection.
It contains powerful TCP/IP and ModBus TCP connecting circuitry with transfer rates of 10 and
100Mbits/s.

Internal connection:

34-pin connector on flat cable

for Slot-4

External
connection:

RJ-45 connecting socket in holding

plate

Transfer rate:

10Mbits/sec (10BaseT , Ethernet) and
100Mbits/sec (100BaseTx, Fast
Ethernet)
Auto-detection (10/100, HalfDX/FullDX)

Connection mode:

Network

Protocol:

ModBus-TCP

Transport:

TCP/IP or UDP/IP

Certificates:

Compatible with ModBus-TCP standard
of ModBus organization
suitable for industrial applications CE,
UL, cUL

Cable:

Twisted pairs, screened
e.g. patch cable CAT5
Autolink (straight or crossover)

Cable impedance:

150 Ohm

Cable length to
HUB:

Max. 115 m

Dimensions
(LxWxH):

87 x 55 x 15mm Potential isolation:

Yes

Weight:

125 g


Application: ModBus TCP as a Fieldbus interface
The IP-Address and the Subnet-Mask are set at Fieldbus parameter FP 96 und 97. (see chapter
4.7.7 and Error! Reference source not found.).

Take care, that switches 1 - 8 are set to (OFF)