beautypg.com

Fairbanks X SERIES PR 5410 Process Indicator User Manual

Page 77

background image

Section 4: Commissioning

10/08 77

51207 Revision 1

Set SPAN failed

Load below deadload

The weight on the scale is less than the dead load after input of the
weight value.

The next step is calculation of the test value with [Test] (see Chapter 0), and calibration is
completed with

(see Chapter 4.5.12).

Determining span without weight

WP A/Calibration

Max

3000 d

3000 kg

Scale interval

3000 d

1 kg

Deadload at

3.00 kg

0.001000

Max at

3000.00

kg

0.000000

Not calibrated

Sensitivity

833.33

4.000000

by load

by mV/V

by data

Linear.

Test


4.5.7 Calibration with mV/V Value

The scale can be calibrated without weights. During input of the load cell mV/V value, the
acceleration of gravity at the place of installation can be taken into account. The STAR load cell
data is based on the acceleration of gravity effective at Hamburg, Germany: 9.81379 m/s².

Calculation of the average load cell sensitivity:
With D1 specification load cells, the use of sensitivity C given in the data sheet is sufficient.
The average load cell sensitivity C

Avr

is calculated as follows:

Ran

1

+

...

+

Ra2

1

+

Ra1

1

Ran

Cn

+

...

+

Ra2

C2

+

Ra1

C1

=

C

Avr

The formula is simplified when the output resistance Ra for the load cells is almost equal:

C

n

1

=

C

Avr


Span: Calculation of the equivalent input voltage in mV/V
Span indicates the equivalent input voltage in mV/V related to the maximum capacity (Max) of the
scale. It is calculated as follows:

cells)

load

of

number

*

load

(nominal

capacity

cell

load

[mV/V

C

y

sensitivit

cell

load

capacity

maximum

=

[mV/V]

Span

Avr

]

*


Dead load:

Calculation of the equivalent input voltage in mV/V

The input voltage in mV/V equivalent to the dead load can be calculated by using the dead load
rather than the maximum capacity in the formula specified above.
Normally, calculation of the dead load (scale without load/empty hopper) is not necessary.
Subsequent dead load correction (as described in Chapter 0) can be used for later re-determination
of the dead load, when the scale/hopper is empty.


Example: Load cell(s) with rated output of 2mV/V at nominal load of 2000 kg, dead load 500 kg,
load cell supply voltage 12 VDC