Section 3: Installing the Instrument and Plug-In Cards
10/08 52
51207 Revision 1
3.5 C
ONNECTING
L
OAD
C
ELLS
Load cells or analog platforms (e.g., from the CAPP series) can be connected.
The supply voltage is protected from short circuit and overload.
The card is fitted with a solder link (factory setting: closed; see Chapter 3.5.5), which should be
opened only when the supply voltage and thus also the sense voltage are reduced to below approx.
+/- 4 VDC.
Terminal block
Connection
Description
+M
+ meas.
+ signal/LC output
- M
- meas.
- signal/LC output
+V
+ supply
+ supply/excitation
+S
+ sense
+ sense
- S
- sense
- sense
- V
- supply
- supply/excitation
Housing
GND
shield/ground
3.5.1 Connecting a Load Cell with 4-Wire Cable
Provide links
between + supply and + sense and
between – supply and - sense
directly at the terminal block.
The cable colors shown above are applicable to the PR 62.. series load cells.
Before connecting, check the assignment of cable colors in the load cell manual.
3.5.2 Connecting PR 6221 Load Cells
See PR 6021/08, -/68 operating manual.