Fairbanks X SERIES PR 5410 Process Indicator User Manual
Page 20
Section 3: Installing the Instrument and Plug-In Cards
10/08 20
51207 Revision 1
3.3.1 Network Port
The network port is built in as standard equipment. The port contains powerful TCP/IP connection
circuitry with transfer rates of 10 or 100 Mbit/sec. The LEDs on the connector indicate whether the
port is functioning.
Transfer rate:
10 Mbit/s, 100Mbit/s,
full / half duplex, auto-detection
Connection method: Point to point
Cable:
CAT 5 patch cable, shielded twisted
pair
Cable impedance:
150 ohms
Electrical isolation: Yes
Cable length :
Max. 115 m
Connection :
RJ-45 socket on back panel of housing
Remote operation of the PR 5410 indicator from the PC
is possible; install version 3.3.7 VNC program on the
PC. For setting the network address, see Chapter
4.2.4.
3.3.2 Standard RS-232 Interface
The instrument is provided with a built-in RS-232 interface that is accessible on the back panel of
the housing. This interface is configurable, and can be used, for example, for data transmission to
a remote display or a printer.
Number of
channels:
1
Type:
RS-232, full duplex
Transfer rate:
300 to 115K2 bit/s
Parity:
none, odd, even
Data bits:
7 / 8 bits
Input signal level:
logic 1 (high) - 3 ... - 15 V
logic 0 (low) + 3 ... + 15 V
Output signal level: logic 1 (high) - 5 ... - 15 V
logic 0 (low) + 5 ... + 15 V
Number of signals:
2 output signals (TXD,
RTS)
2 input signals (RXD, CTS)
Electrical isolation: none
Cable type:
shielded twisted pair
(e.g. LifYCY 3x2x0,20),
1 pair of wires for GND
Connection:
9-pin D-Sub socket (female) Cable length:
max. 15 m