Section 4: Commissioning
10/08 82
51207 Revision 1
[Test mode]
With [Absolute], the test value is determined when the test is called. With [Relative], the deviation
from the initially stored test value is displayed; see Chapter 0.
[W & M]
Setting for 'legal-for-trade' mode; select [None], [OIML], [NTEP] (for USA) or [NSC] (for Australia);
see Chapter 0.
[Standstill time]
Parameters [Standstill range] and [Standstill time] are required for determining the mechanical
stability of the scale. Input in seconds; permissible range: 0.01 to 2 sec. If 0 is set, stability is not
checked. The stability time must not be less than the measurement time.
[Standstill range]
The mechanical stability of the scale can be detected as long as any changes in the weight value
are within this range; permissible range 0.01d to 10.00d. In ‘legal-for-trade’ mode, select <= 1 d.
WP A/Calibration
Tare timeout
2.5 s
Zeroset range
50.00 d
Zerotrack range
0.25 d
Zerotrack step
0.25 d
Zerotrack time
0.0 s
Overload
9 d
[Tare timeout]
Enter a timeout value between 0.1 and 25 s for a taring/zero set command that cannot be executed
(e.g., if scale mechanically unstable, filter settings faulty, resolution too high, stability condition too
narrow).
[Zeroset range]
Determine a +/- range around the zero point determined by the dead load during calibration; within
this range:
- the displayed gross weight can be set to zero by pressing the zero-setting key (or by a
corresponding external command), and
- automatic zero tracking is active
Available range: 0.00 d to 10000.00d
In 'legal-for-trade' mode a value <= 2 % of Max. must be entered. Example: 60 d for 3000e, class III.
[Zerotrack range]
Range within which automatic zero tracking compensates deviations; 0.25 to 10000.00d.
In 'legal-for-trade' mode a value of 0.25 d has to be entered.
[Zerotrack step]
Step for automatic tracking; 0.25 to 10d. In 'legal-for-trade' mode a value of 0.25 d has to be
entered.
[Zerotrack time]
Enter a time interval for automatic zero tracking within 0.0 (tracking switched off) and 25 s.
In 'legal-for-trade' mode a value of 1 s has to be entered.