Section 3: Installing the Instrument and Plug-In Cards

10/08 28

51207 Revision 1


PR 5510/04 RS-422/485
When mounting, the RS-485/422 interface must be configured by DIL switch S101 on the card.
Using RS-485 is compulsory with a multi-point connection (tristate status). The RS-485 interface
can be used also for point-to-point connection. Like 2-wire or 4-wire connections, this is dependent
on the other communicating units.
A 2-wire connection is half-duplex and cannot send and receive simultaneously. It requires
corresponding driver programming (see relevant instrument manual).

Factory setting

Switch S101

Settings for RS-422/ 485

1: Tristate enable:

OFF – RS-422

ON – RS-485

2: Rx enable

OFF – 4-wire

ON – 2-wire

3: Rx pull-up resistor:

OFF – not connected ON - (RxB 1k54 +V)

4: Rx bus termination:

OFF – not connected ON - (RxA 205E

RxB)

5: Rx pull-down resistor: OFF – not connected ON - (RxA 1k54 -V)



Overview of which switches must be closed (ON) for which mode:

Two-wire system

Four-wire system

S101

Point to point

Bus

Point to point

Bus

Master

RS-485
1, 2, 3, 4, 5 =
on

RS-485
1, 2, 3, 4, 5 = on

RS-422
4 = on

RS-422
3, 4, 5 = on

Individual slave

RS-485
1, 2 = on

-

RS-422
4 = on

-

Other slaves

-

RS-485
1, 2 = on

-

RS-485
1 = on (default)

Last slave

-

RS-485
1, 2, 3, 4, 5 = on

-

RS-485
1, 3, 4, 5 = on