Fairbanks X SERIES PR 5410 Process Indicator User Manual
Page 101
Section 4: Commissioning
10/08 101
51207 Revision 1
[Weight at 20 mA]
Weight value for 20 mA output
Press
to return to the previous menu [Configuration].
4.9.1 Adapting the Analog Output
The output current can be adapted in small ranges. This is required, if small deviations from the
nominal value occur in a connected PLC.
Press
and select [Show HW-slots]-[Slot 1/2 PR5510/07 analog I/O] to open the menu:
Info/HW-Slots
Builtin
RS 232
Slot 1
PR
5510/07
analog I/O
PR 5510/07 is fitted in Slot 1
Slot 2
-empty-
Slot 3
Builtin
Digital I/O
Slot 4
PR
1721/31
Profibus-DP
Select [PR 5510/07 analog I/O] and confirm with
.
Info/HW-Slots
PR5510/07 on slot
1
In use by PLC task
2
Analog output
0.0000 mA Select with
Stop PLC Stop I/O
Adjust
Reset
Press [Adjust]
Adapt analog output ?
Safety prompt: Reply [Yes] to start adapting.
Info/HW-Slots/Adjust Analog Output Slot 1
Output
4.000 mA
Measured
4.004 mA
Enter e.g. the value for 4 mA measured by the connected PLC under [Measured].
After pressing
, the 2nd value (20 mA) is displayed:
Info/HW-Slots/Adjust Analog Output Slot 1
Output
20.000 mA
Measured
20.010 mA
Enter e.g. the value for 20 mA measured by the connected PLC under [Measured].
Save settings ?
Reply [Yes] to validate the changes, or
[No] to keep the previous values.
If you want to return to the factory settings (4 mA and 20 mA):
Press [Reset]: A safety prompt is displayed:
Reset to default ?
Reply [Yes] for reset to the factory settings, or
[No], if you want to keep the entered values unchanged.